C200H-PS211 Omron, C200H-PS211 Datasheet - Page 144

no-image

C200H-PS211

Manufacturer Part Number
C200H-PS211
Description
EXPAN. P/S: 24VDC
Manufacturer
Omron
Datasheet

Specifications of C200H-PS211

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
5
148
SYSMAC LINK Token
Bus Network
Specifications
Network topology
Number of nodes
Transmission media
Distance
Transmission speed
Functions
PLC interfaces
Message size
Data link capacity per node
Data link capacity per network
Diagnostics
C200H
C1000H, C2000H
CV500, CV1000
Communication Systems
SYSMAC LINK is a high-speed token bus network designed to transfer
large amounts of control data in real time between small and large rack
PLCs. A variety of methods can be used to initiate communications
between nodes; automatic data link allows transfer of data without any
special programming; custom data link tables can be used for special data
transfers between nodes. Each node can initiate transfers in send/receive
mode using ladder logic instructions. This also allows each PLC to control
communications and network data handling. Any node can be monitored
or programmed using the Factory Intelligent Terminal (FIT) connected to a
node on the network.
The following guidelines should be taken into account when configuring a
SYSMAC LINK network:
Token bus
62 nodes per network
Wire: 75Ω impedance co-axial cable
Fiber-optic: 200 µ HPCF duplex fiber-optic cable
Wire: 1 km (0.62 mile) total
Fiber-optic: 800 m (0.5 mile) between nodes, 10 km (6.2 miles) total
2 Mbps
Send, Receive, Deliver commands with FINS support (CV PLCs), automatic and
custom data link
C200H, C1000H, C2000H, CVM1, CV500, CV1000, CV2000
512 bytes (256 words) maximum
Link relay area: 64 words (128 bytes)
Data memory area: 254 words (508 bytes)
918 words max.
2966 words max.
2966 words max.
Transmission path backup (fiber-optic backloop), failed node bypass, polling link
backup, self-diagnostic and echo-back test, watchdog timer, error detection
12 Communication Sys-
High-speed token bus communications
Large amounts of data transfered between PLCs or computers in a
single command
Automatic data link, custom data link, and peer-to-peer event
communications options
Send and receive instructions for PLC-initiated communications
SYSMAC LINK can be connected to CV, C200H, C1000H, or C2000H
simplex systems
At least one SYSMAC LINK module per PLC system
One SYSMAC LINK Network Support Board per computer (co-axial
only)
tems

Related parts for C200H-PS211