LC1D95E7 SQUARE D, LC1D95E7 Datasheet - Page 3

no-image

LC1D95E7

Manufacturer Part Number
LC1D95E7
Description
CONTACTOR 575VAC 95AMP IEC +OPTIONS
Manufacturer
SQUARE D
Datasheet
Complementary
Environment
Coil technology
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non-overlap time
Insulation resistance
IP degree of protection
Protective treatment
Pollution degree
Ambient air temperature for operation
Ambient air temperature for storage
Permissible ambient air temperature around the de-
vice
Operating altitude
Fire resistance
Flame retardance
Mechanical robustness
Height
Width
Depth
Product weight
Mechanical durability
Operating rate
Without built-in suppressor module
0.85...1.1 Uc at 55 °C operational 60 Hz
0.8...1.1 Uc at 55 °C operational 50 Hz
0.3...0.6 Uc at 55 °C drop-out 50/60 Hz
245 VA at 20 °C (cos ϕ 0.75) 50 Hz
245 VA at 20 °C (cos ϕ 0.75) 60 Hz
26 VA at 20 °C (cos ϕ 0.3) 50 Hz
26 VA at 20 °C (cos ϕ 0.3) 60 Hz
6...10 W at 50/60 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
25...400 Hz
5 mA for signalling circuit
17 V for signalling circuit
1.5 ms on energisation (between NC and NO contact)
1.5 ms on de-energisation (between NC and NO contact)
> 10 MOhm for signalling circuit
IP2x front face conforming to IEC 60529
TH conforming to IEC 60068-2-30
3
-5...60 °C
-60...80 °C
-40...70 °C at Uc
3000 m without derating in temperature
850 °C conforming to IEC 60695-2-1
V1 conforming to UL 94
Shocks contactor closed 10 Gn for 11 ms
Shocks contactor open 8 Gn for 11 ms
Vibrations contactor closed 3 Gn, 5...300 Hz
Vibrations contactor open 2 Gn, 5...300 Hz
127 mm
85 mm
130 mm
1.61 kg
4 Mcycles
3600 cyc/h at <= 60 °C
3