K8AB-AS1 200/230VAC Omron, K8AB-AS1 200/230VAC Datasheet - Page 2

20-500mA 1-phs Current Monitor

K8AB-AS1 200/230VAC

Manufacturer Part Number
K8AB-AS1 200/230VAC
Description
20-500mA 1-phs Current Monitor
Manufacturer
Omron
Series
K8ABr

Specifications of K8AB-AS1 200/230VAC

Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
K8AB-AS1-200-230VAC
K8ABAS1200230VAC
Z2804
Ordering Information
■ List of Models
Note: The K8AB-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not
■ Accessory (Order Separately)
OMRON CT
Other CTs
Ratings and Specifications
■ Input Range
Note: The K8AB-AS3 is designed to be used in combination with an OMRON K8AC-CT200L Current Transformer (CT). (Direct input is not
* The range is selected using connected terminals.
0 to 1 A AC,
0 to 5 A AC
K8AB-AS1
K8AB-AS2
K8AB-AS3
CT current on secondary side
Single-phase Current Relay
Current Transformer
Model
possible.)
possible.)
0 to 20 mA AC/DC
0 to 100 mA AC/DC
0 to 500 mA AC/DC
0 to 1 A AC/DC
0 to 5 A AC/DC
0 to 8 A AC/DC
0 to 100 A AC
0 to 200 A AC
Range*
10 to 100 A AC,
20 to 200 A AC
K8AB-AS2
2 to 20 mA AC/DC,
10 to 100 mA AC/DC,
50 to 500 mA AC/DC
0.1 to 1 A AC/DC,
0.5 to 5 A AC/DC,
0.8 to 8 A AC/DC
10 to 100 A AC,
20 to 200 A AC
(See note.)
Measuring current
Applicable Relay
Input range
I1-COM
I2-COM
I3-COM
I1-COM
I2-COM
I3-COM
I2-COM
I3-COM
Connection terminal
K8AB-AS3
Applicable Relay
24 VAC/DC
100-115 VAC
200-230 VAC
24 VAC/DC
100-115 VAC
200-230 VAC
24 VAC/DC
100-115 VAC
200-230 VAC
Supply voltage
2 to 20 mA AC/DC,
10 to 100 mA AC/DC,
50 to 500 mA AC/DC
0.1 to 1 A AC/DC,
0.5 to 5 A AC/DC,
0.8 to 8 A AC/DC
10 to 100 A AC,
20 to 200 A AC
(See note.)
Measuring current
K8AC-CT200L
K8AB-AS1 24 VAC/DC
K8AB-AS1 100-115 VAC
K8AB-AS1 200-230 VAC
K8AB-AS2 24 VAC/DC
K8AB-AS2 100-115 VAC
K8AB-AS2 200-230 VAC
K8AB-AS3 24 VAC/DC
K8AB-AS3 100-115 VAC
K8AB-AS3 200-230 VAC
Approx. 5 Ω
Approx. 1 Ω
Approx. 0.2 Ω
Approx. 0.12 Ω
(Load: 0.5 VA)
Approx. 0.02 Ω
(Load: 1.5 VA)
Approx. 0.02 Ω
(Load: 3 VA)
Using OMRON CT
Using OMRON CT
Input impedance
Model
Model
Continuous input:
120% of maximum input
1 s max.:
150% of maximum input
Continuous input:
120% of maximum input
30 s max.:
200% of maximum input
1 s max.:
600% of maximum input
Overload capacity
K8AB-AS
2