K8AC-CT200L Omron, K8AC-CT200L Datasheet - Page 6

no-image

K8AC-CT200L

Manufacturer Part Number
K8AC-CT200L
Description
20-200A Current Transformer
Manufacturer
Omron
Datasheet

Specifications of K8AC-CT200L

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Nomenclature
■ Front
6
Relay status indicator
(See notes 1 and 2.)
(See notes 1 and 2.)
Power indicator
Alarm indicator
Terminal block
Terminal block
Single-phase Current Relay
Current knob (SV)
Hysteresis knob (HYS.)
Operating time knob (T)
Startup lock time knob
(LOCK)
K8AB-AS
Indicators
Setting Knobs
Note: 1. Use either a solid wire of 2.5 mm
Power indicator
(PWR: Green)
Relay status indicator
(RY: Yellow)
Alarm indicator (ALM: Red) Lit when there is an overcurrent or
Current knob (SV)
Hysteresis knob (HYS.)
Operating time knob (T)
Startup lock time knob
(LOCK)
2. Tightening torque
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted
into the terminal must be 8 mm or less to maintain dielectric
strength after connection.
Recommended ferrules
Recommended: 0.49 N·m
Maximum: 0.54 N·m
Phoenix Contact
• Al 1,5-8BK (for AWG16)
• Al 1-8RD (for AWG18)
• Al 0,75-8GY (for AWG18)
Item
Item
For 2.5 mm
smaller solid wires
8 mm max.
2
or
Lit when power is being supplied.
Lit when relay is operating.
undercurrent.
The indicator flashes to indicate the
error status after the input has
exceeded the threshold value while the
operating time is being clocked.
Used to set the current to 10% to 100%
of maximum measuring current.
Used to set the rest value to 5% to 50%
of the operating value.
Used to set the operating time to 0.1 to
30 s.
Used to set the startup lock time to 0 to
30 s.
For ferrules with
insulating sleeves
2
Cat. No. N142-E1-02
maximum or a ferrule with
Meaning
8 mm max.
Usage