Switch Output Configuration
External Connections
The stop/emergency stop switch uses DPST-NC contact + NO bit. Of these,
DPST-NC contacts are used for external hardware outputs. The remaining NO
bit can be allocated any bit in the internal memory or in the host (PLC) mem-
ory.
Six function switches can be allocated any bits in the internal memory or in
the host (PLC) memory. Four of the function switches can be output to exter-
nal contact outputs.
The enabling switch (DPST-NO) can also be output to external contact out-
puts.
Use a Special Cable (NSH5-232/422-CW-@@M, UL type: NSH5-232/422UL-
@@ M ), loose-wires and D-Sub connector on one end) to connect the signals
as follows:
Stop/emergency stop switch
(DPST-NC contact + NO bit)
• Setting parameters and monitoring operation anywhere in expansive facil-
• Emergency stop switch/stop switch
• Enabling switch
• Serial communications (RS-232C or RS-422A)
• Function switches
10 function switches
ities
When using as a safety system, connect to safety components. (Do not
connect to the PLC.)
When using as a safety system, connect to safety components. (Do not
connect to the PLC.)
Connect to the serial port of the PLC.
Connect to an DC Input Unit of the PLC.
The hard-wired outputs operate even when the PT power supply is OFF.
Enabling switch
(DPST-NO)
Enabling switch outputs
(DPST-NO)
External
output
F10
F1
F2
F3
F4
F5
F6
F7
F8
F9
4 function
switch outputs
Allocation
24-VDC power supply
Stop/emergency stop
switch outputs (DPST-NC)
Stop/emergency stop switch
Allocation
NSH5
Internal memory
F5
F9
F10
F4
F3
F8
Color STN LCD
RS-232C
or RS-422A
or
Section 1-1
Stop/emergency stop switch
Host (PLC) memory
F5
F9
F10
F4
F3
F8
5