CS1D-BC042D Omron, CS1D-BC042D Datasheet - Page 536
CS1D-BC042D
Manufacturer Part Number
CS1D-BC042D
Description
CS1D Dual CPU Exp
Manufacturer
Omron
Datasheet
1.CS1D-SP002.pdf
(638 pages)
Specifications of CS1D-BC042D
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
- Current page: 536 of 638
- Download datasheet (12Mb)
The tables list the functions of Auxiliary Area words and bits in order of their addresses. For a list of Auxiliary
Area words and bit by function, refer to SECTION 8 Memory Areas.
The Auxiliary Area consists of read-only words A000 to A447 and read/write words A448 to A959.
Read-only Words
The following words and bits are written by the system to provide information on PLC operation.
A019
Words
Address
Previous Cause of Switching to Simplex Operation (Duplex CPU Systems only)
A01900
A01901
A01902
A01903
A01904
A01906
A01908
A01909
A01912
A01915
Bits
Duplex
Verifica-
tion Error
Switch
Flag
Duplex
Bus Error
Switch
Flag
Duplex Ini-
tialization
Error
Switch
Flag
CPU Unit
Setting
Switch
Flag
CPU Error
(WDT)
Switch
Flag
FALS
Instruc-
tion Error
Switch
Flag
Cycle
Time
Overrun
Switch
Flag
Program
Error
Switch
Flag
Fatal Inner
Board
Error
Switch
Flag
Memory
Error
Switch
Flag
Name
ON: A duplex verification error caused the
previous switch from duplex to simplex
operation.
ON: A duplex bus error caused the previ-
ous switch from duplex to simplex opera-
tion.
ON: An error during duplex initialization
caused the previous switch from duplex to
simplex operation and duplex operation
was never started.
ON: Changing the CPU Unit’s switch from
USE to NO USE caused the previous
switch from duplex to simplex operation.
ON: A CPU Unit error (WDT) caused the
previous switch from duplex to simplex
operation.
ON: Execution of an FALS instruction
caused the previous switch from duplex to
simplex operation.
ON: Exceeding the cycle time caused the
previous switch from duplex to simplex
operation.
ON: A program error caused the previous
switch from duplex to simplex operation.
ON: A fatal Inner Board error caused the
previous switch from duplex to simplex
operation. (Process-control CPU Units
only)
ON: A memory error caused the previous
switch from duplex to simplex operation.
Auxiliary Area Allocations
Function
Appendix B
ON: Switched to
simplex opera-
tion for duplex
verification error
OFF: Normal
ON: Switched to
simplex opera-
tion for duplex
bus error
OFF: Normal
ON: Switched to
simplex opera-
tion for duplex
initialization
error
OFF: Normal
ON: Switched to
simplex opera-
tion for CPU set-
ting
OFF: Normal
ON: Switched to
simplex opera-
tion for CPU
error
OFF: Normal
ON: Switched to
simplex opera-
tion for FALS
instruction
OFF: Normal
ON: Switched to
simplex opera-
tion for cycle
time error
OFF: Normal
ON: Switched to
simplex opera-
tion for program
error
OFF: Normal
ON: Switched to
simplex opera-
tion for fatal
Inner Board
error
OFF: Normal
ON: Switched to
simplex opera-
tion for memory
error
OFF: Normal
Settings
change
Held
Status
mode
after
Held
startup
Status
at
Data from
A023 is
stored
when
duplex
operation
is recov-
ered.
Timing
---
settings
Related
flags,
501
Related parts for CS1D-BC042D
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
CS1D Dual IO Control Unit
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual IO Interface Unit
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual Exp Rack
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
CS1D Dual IO Exp
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
G6S-2GLow Signal Relay
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Compact, Low-cost, SSR Switching 5 to 20 A
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet: