SMA915D BANNER ENGINEERING, SMA915D Datasheet - Page 3

no-image

SMA915D

Manufacturer Part Number
SMA915D
Description
SMA915D SCANNER W/RELAY
Manufacturer
BANNER ENGINEERING
Datasheet

Specifications of SMA915D

Brand/series
Valu-Beam®
Current, Switching
5 A
Function
Proximity
Ip Rating
IP66
Mounting Type
Threaded
Output
Relay, SPDT
Primary Type
Photoelectric
Range, Measurement
760 mm
Sensing Mode
Diffuse
Technology
Photoelectric
Termination
Cable
Voltage, Supply
130 VAC
Voltage, Switching
250/30 VAC/VDC
Lead Free Status / Rohs Status
RoHS Compliant part
VALU-BEAM –
Supply Voltage and Current
Output Configuration
Output Rating
Output Protection Circuitry
Output Response Time
Adjustments
Indicators
Construction
Environmental Rating
Connections
Operating Conditions
Application Notes
Certifications
Supply Protection Circuitry
915 Series
SMW915 Series: 12 to 28V ac or dc at 50 mA maximum, exclusive of load
SMA915 Series: 90 to 130V ac (50-60 Hz) at 20 mA maximum, exclusive of load
SMB915 Series: 210 to 250V ac (50-60 Hz) at 20 mA maximum, exclusive of load
Exceptions: SMA91E and ESR emitters, which operate from 10-250V ac (50-60 Hz) or dc (10 mA max.)
Protected against transient voltages
One internal “form C” (single-pole double-throw) electromechanical relay
Max. switching power (resistive load): 150 W, 600 VA
Max. switching voltage (resistive load): 250V ac or 30 V dc (120V ac max. per UL & CSA)
Max. switching current (resistive load): 5A
Min. voltage and current: 1 amp at 5V dc, 0.1 amp at 24V dc
Peak switching voltage: 750V ac (transient suppression recommended)
Mechanical life of relay: 10,000,000 operations
Protected against false pulse on power-up
20 milliseconds ON and OFF; independent of signal strength
(NOTE: 100 millisecond delay on power-up; relay de-energized during this time)
Sensitivity control on rear of sensor allows precise gain setting (turn clockwise to increase gain)
Top-mounted red LED indicator lights whenever the sensor sees “light” condition.
Models SMA91E and SMA91ESR emitters have visible-red “tracer beam” which indicates “power on” and
enables easy “line-of-sight” alignment.
Reinforced black thermoplastic polyester housing, totally encapsulated, molded acrylic lenses and stainless
steel hardware
Meets NEMA standards 1, 2, 3, 3S, 4, 4X, 12 and 13; IEC IP66
Emitters: PVC-jacketed 2 m (6.5') or 9 m (30') cable or 3-pin Mini-style quick-disconnect (QD) fitting
available. See page 8.
All Other Sensors: PVC-jacketed 2 m (6.5') or 9 m (30') cable or 5-pin Mini-style quick-disconnect (QD)
fitting available. See page 8.
Temperature:
Maximum relative humidity: 90% at 50°C (non-condensing)
Install transient suppressor (MOV) across any output contact which switches an inductive load
915 Series Specifications
-40° to +50° C (-40° to +122°F)

Related parts for SMA915D