E5-648-C2421 EATON CUTLER HAMMER, E5-648-C2421 Datasheet - Page 6

no-image

E5-648-C2421

Manufacturer Part Number
E5-648-C2421
Description
PRESET COUNTER, 6-DIGIT, 90VAC TO 260VAC
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of E5-648-C2421

No. Of Digits / Alpha
6
Digit Height
9mm
Supply Voltage Range
90VAC To 260VAC
Power Consumption
750VA
Counting Speed
50kHz
Operating Temperature Range
-20°C To +65°C
7.8.3 Setting the Basic Function
7.8.4 Pulse Counter
7.8.4.1 Main menu for Signal and Control inputs
Input polarity
Filter for signal inputs InpA and InpB
Instruction leaflet IL05407002E
Effective October 2010
6
eaton corporation www.eaton.com
Basic function menu
Programming menu
Pulse counter (7 .8.4)
Programming menu
Timer/Hour meter (7 .8.6)
Programming menu
Tacho/Frequency meter (7 .8.5)
Main menu for programming the
signal and control inputs
PNP: switching to Plus
for all inputs in common
NPN: switching to 0V
for all inputs in common
Maximum count frequency
Damped to approx. 30 Hz
(for control with mechanical contacts)
Count Input mode
User input
Count/Direction
INP A: count input
INP B: count direction input
Differential counting [A – B]
INP A: count input add
INP B: count input sub
Totalizing [A + B]
INP A: count input add
INP B: count input add
Quadrature input
INP A: count input 0°
INP B: count input 90°
Quadrature with pulse doubling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A will be counted
Quadrature x4
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A
and INP B will be counted.
Ratio measurement [A/B]
Inp A: count input A
Inp B: count input B
Percentage differential counting
[(A – B)/A in %]
Inp A: count input A
Inp B: count input B
When the MPI input is activated, the display
is “frozen” and remains “frozen” until the
MPI input is deactivated. Internally the
preset counter continues counting
When the MPI input is activated, the
current count value for the preset
that has just been selected will be adopted
as the new preset value. See also 7 .9
When the MPI input is activated, the
preset counter will be set to the value
specified in the parameter SEtPt.
See also 7 .10
electronic preset counter
with two presets
E5-648-C242x