Installation
one serial mode may be used at a time per port. Each communication port includes a set of 12 jumpers divided into two columns. These
jumpers must be set according to the serial mode desired.
labeling (some jumpers are labeled with C designations for COM2 and D designations for COM3). In this figure, no jumpers have been
installed.
1
Terminals
(Com 2 or
With RS-232, the +5 VDC may be used to power devices with light current demands
such as barcode readers or hand-held terminals. Leave this jumper out if you do not
need this voltage source.
Comm.
Com 3)
The two serial ports (COM2 and COM3) of the M4SSER may be configured by setting jumpers for either RS-232 or RS-485/422. Only
The figure below shows the two sets of jumpers as they appear on the M4SSER. Note that the two sets are identical except for the
• For RS-232, install all jumpers to the left. In addition, install all termination jumpers (C1–C4 or D1–D4) to ensure reliable
• For RS-485/422, install all jumpers to the right. Choose jumper location for 2-wire/4-wire and for termination based on your
2
3
4
5
6
7
1
Inside Sales: (800) 321-OPTO • Product Support: (800) TEK-OPTO • (951) 695-3080 • Fax: (951) 695-3017 • E-mail: sales@opto22.com
communications, and remove the 2-wire/4-wire jumper (C2W or D2W).
system (see table below, right).
NOTE: For RS-232, leave out JP1/JP8 if you are not
using the +5 VDC power source (see table below, left).
Columns)
(Jumpers
+ 5 VDC
in Left 2
RS-232
GND
CTS
DTR
RTS
TX
RX
JUMPERS
1
RS-485 (Jumpers in Right 2 columns)
Jumper In)
(C2W/D2W
TX/RX+
TX/RX-
2-Wire
IRQ +
IRQ -
GND
NC
NC
Jumper Out)
(C2W/D2W
4-Wire
IRQ +
IRQ -
TX +
GND
RX +
TX -
RX -
2
C2W/D2W
Jumper
For RS-232, remove the C2W/D2W jumper and install
jumpers on C1 through C4 or D1 through D4.
For RS-485/422, set jumpers C1 through C4 or D1 through
D4 all the same, depending on whether the M4RTU/DAS is
physically the last unit in the communication link (jumpers in)
or not (jumpers out).
C1/D1
C2/D2
C3/D3
C4/D4
INTERFACES
2
2
2
2
Function when
CONTROLLER
Terminated
Terminated
Terminated
Terminated
Jumper In
2-Wire
MODULAR
Function When
Not Terminated
Not Terminated
Not Terminated
Not Terminated
Jumper Out
4-Wire
page 6/7