LRCD220 Megger, LRCD220 Datasheet

TESTER, LOOP+RCD

LRCD220

Manufacturer Part Number
LRCD220
Description
TESTER, LOOP+RCD
Manufacturer
Megger
Datasheet

Specifications of LRCD220

Insulation Tester Type
RCD
Insulation Test Resistance
2kohm
Operating Temperature Range
-5°C To +40°C
External Height
203mm
External Width
148mm
External Depth
78mm
Weight
980g
Battery Size Code
AA
External
RoHS Compliant
LRCD200 Series
Combined Loop and RCD Testers
DESCRIPTION
The LRCD200 series is the latest generation of combined
non-tripping loop tester and RCD test instruments that
provide simple, affordable and flexible test tools for
electrical contractors testing energised circuits.
All LRCD200 series instruments are supplied with a Megger
calibration certificate.
Three instruments are available:
LRCD200
LRCD 210
LRCD220
All three instruments will not trip RCDs rated at 30 mA or
greater during loop testing, even electronic RCDs.
This instrument provides 3 phase safe non trip
loop testing and 1xI tests of 10mA to 500mA
RCDs.
NOT SUITABLE FOR UK APPLICATIONS.
This instrument provides three phase safe non-
trip loop testing and 1/2I, I, and 5I RCD testing
for standard, selective and DC RCDs. Suitable for
domestic installers testing to UK Part P
requirements.
As the LRCD210 with the addition of 110 V loop
testing and 2 wire fast testing, plus phase to
phase and phase to earth measurement.
GENERAL FEATURES
All instruments are designed using the new Megger
electricians tester case, providing tough rubber armouring,
built-in front cover, weatherproof to IP54 and easy-to-use
functions and layout.
The instruments can be hung around the neck or hand
held and will not slip if placed on a bench or shelf.
Test leads can remain attached with the front cover open
or closed.
L-N-E connection indicator LEDs show connection status
and reverse polarity supplies.
Non-tripping loop testing
The Megger ‘No-Trip’ loop test is designed for loop testing
on circuits where an RCD is fitted. The RCD is guaranteed
not to trip if rated 30 mA or greater.
The ‘No-Trip’ loop test is also guaranteed not to trip
electronic RCDs.
All LRCD testers offer
Non-trip loop tester
RCD testing from 10 mA to 1000 mA
Extremely easy and safe to use
Built-in protective front cover
Tough Rubber armoured case
Weatherproof
3 year warranty
Non-tripping Loop test. RCDs rated 30 mA or greater are
not tripped by the loop test, even electronic RCDs.
3 wire low current non-tripping loop test provides
measurements from 0.01 ohms to 2 kohms.
Auto-ranging tests.
Combined Loop and RCD Testers
LRCD200 Series

LRCD220 Summary of contents

Page 1

... I, and 5I RCD testing for standard, selective and DC RCDs. Suitable for domestic installers testing to UK Part P requirements. LRCD220 As the LRCD210 with the addition of 110 V loop testing and 2 wire fast testing, plus phase to phase and phase to earth measurement. ...

Page 2

... AC, AC selective, DC and DC selective RCD type selection 0/180 degree selection Ramp testing Touch voltage selection Optional Touch voltage display Additionally the LRCD210 and LRCD220 offers: 1 and RCD testing plus the LRCD220 offers: 1000 mA RCD testing Display backlight Test lock Combined Loop and RCD Testers ...

Page 3

... HI current Line/Earth loop test 2 wire (LRCD220 only) Supply: 100V - 480 V Frequency: 45Hz to 65Hz Nominal Test Current ...

Page 4

... Norristown USA, Toronto CANADA, Mumbai INDIA, Trappes FRANCE, Sydney AUSTRALIA, Madrid SPAIN and the Kingdom of BAHRAIN. LRCD200 Series Combined Loop and RCD Testers Order Code LRCD210-EN-AU LRCD220-EN-AU 6220-782 6220-790 6220-784 6231-586 6111-694 Registered to ISO 9001:2000 Reg no. Q 09290 Registered to ISO 14001 Reg no. EMS 61597 LRCD200_DS_en_V01 www ...