P01.1408.03D CHAUVIN ARNOUX, P01.1408.03D Datasheet - Page 2

MEGOHMMETER, CA6525

P01.1408.03D

Manufacturer Part Number
P01.1408.03D
Description
MEGOHMMETER, CA6525
Manufacturer
CHAUVIN ARNOUX
Datasheet

Specifications of P01.1408.03D

Insulation Tester Type
Digital Megohmmeter
Insulation Testing Voltage
250 V, 500 V, 1000 V
Insulation Test Resistance
50 K To 2000 M
External Height
211mm
External Width
64mm
Testing electrical
installations and equipment
* automatic voltage display between 0…600 V AC/DC prior to insulation measurements and
measurement locking if U > 25 V.
MEASUREMENT FUNCTIONS
INSULATION*
Range
Resolution
Accuracy
CONTINUITY
Beep sound
Range
Resolution
Accuracy
Lead compensation
RESISTANCE
Range
Resolution
Accuracy
MEASUREMENT AIDS
Giant Bar graph (Logarithmic)
Back-lit display
ALARM function
TIMER function
Remote control probe
T
C.A 6523 and C.A 6525 make measurement both
straightforward and convenient.
Ergonomics
Measurement aids
Safety
Usability
he innovative range of megohmmeter models C.A 6521,
• Giant back-lit display for extra clarity
• 4000 ct. digital display + logarithmic bar graph for:
• Stand: for use of equipment on table or on the ground
• Casing design: grips firmly in the hand
• Limit values
• Timer function
• Lead compensation
• Automatic voltage detection
• Device protected against external loads
• Safety of the operator
• 6 LR6 batteries for long periods of serviceable use
• Automatic switch-off after 5 min’s for prolonged
• Battery level indicator at each start up to prevent
simultaneous reading of measurement and analogue
variation
Programmable high and low thresholds trigger ‘beep’
sound (no longer necessary to read the value to verify
the result)
Automatic time measurement with stopwatch display
(up to 15 min’s)
Precise measurement in continuity testing guaranteed
The presence of a dangerous voltage level on the test
circuit automatically prevents insulation measurement
from being made
High voltages are discharged from device when
testing is over (capacitive charges)
battery life
being caught out on site
± 3% R ± 5 cts max
50 kΩ… 2000 MΩ
0.01 / 0.1 / 1 MΩ
250 V 500 V
± 3% R ± 1 ct
C.A 6521
C.A 6521
yes, rapid
0… 20 Ω
0.01 Ω
-
-
-
-
-
-
-
-
± 3% R ± 5 cts max
± 3% R ± 2 cts max
100 kΩ… 2000 MΩ
0.1 / 1 / 10 / 100 Ω
500 V 1000 V
0.01 / 0.1 / 1 MΩ
± 3% R ± 1 ct
C.A 6523
C.A 6523
0… 400 kΩ
yes, rapid
optional
0… 20 Ω
0.01 Ω
-
250 V 500 V 1000 V
± 3% R ± 5 cts max
± 3% R ± 2 cts max
0.1 / 1 / 10 / 100 Ω
50 kΩ… 2000 MΩ
0.01 / 0.1 / 1 MΩ
± 3% R ± 1 ct
C.A 6525
C.A 6525
0… 400 kΩ
yes, rapid
0… 20 Ω
optional
0.01 Ω