212359 Megger, 212359 Datasheet - Page 2

INSULATION TESTER, 1000V, 2000MOHM

212359

Manufacturer Part Number
212359
Description
INSULATION TESTER, 1000V, 2000MOHM
Manufacturer
Megger
Datasheet

Specifications of 212359

Insulation Tester Type
Hand Cranked Analogue Megohmmeter
Insulation Testing Voltage
100V, 250V, 500V, 1000V
Insulation Test Resistance
0.1ohm To 2000Mohm
Resistance
2000 Ohms
Current Rating
2 mA
Frequency
60 Hz
Measured Components
Voltages
Safety Rating
2.5 % of Full Scale
Lead Free Status / RoHS Status
na
Lead Free Status / RoHS Status
na
1000 V d.c. when this requirement is specified, also aircraft
and tele-communications equipment can be tested at the
relatively low 100 V d.c. and 110 V to 120 V a.c. systems can
be tested using 250 V d.c.
Test leads with fused prods are available and it is
recommended that these be used when checking that
equipment has been isolated from the supply (by
performing a voltage test), especially in high energy
situations.
SPECIFICATION
Insulation Range
Insulation Resistance: 0.1 Ω - 2000 MΩ (0.1 Ω -1000 MΩ for
MJ160)
Accuracy: ±1.25% of fsd on a 2.8 in. (71.1mm) arc length
Nominal Test Voltages
d.c: 100 V , 250 V , 500 V , 1000 V .
(MJ160 is 50 V , 100 V , 250 V , 500 V)
Accuracy
250 V , 500 V , 1000 V +30%, -0% max.
50 V , 100 V , +40%, -0% max.
Midscale: 4 MΩ (2 MΩ for MJ160)
Short Circuit Current: 1.9 mA
(0.65 mA for MJ160)
Maximum Load Capacitance: 1µF with less than ±0.1" pointer
movement
Discharge: Up to 1 µF capacitance is discharged from 1000 V to
less than 42.4 V in less than 4 secs
Resistance Range
0.1 Ω - 5000 Ω
Test Voltage characteristics
Open circuit Test voltage: 3 V ±0.2 V
Short Circuit Current: 2 mA ±10%
Accuracy: ±1.25% of fsd on a 2.8 in. (71.1mm) arc length:
Safety Voltage Check
Voltage measurement: 0.1 V - 600 V a.c; the meter is RMS
calibrated and average responding
Safety voltage indicator: Indicates the presence of d.c. voltages.
Scaling is not the same as the a.c. meter. True d.c. voltage equals
scale reading divided by 2.22
Accuracy: 2.5% of full scale
Power Supplies
MJ159 and MJ160: Low voltage brushless a.c. generator. Cranking
speed between 130 rpm and 170 rpm
MJ359: Dual operation low voltage brushless a.c. generator or 120
V 50/60 Hz mains (line) supply
MJ459: Six IEC LR6 cells (AA) Battery life: not less than 1300
insulation or Resistance range tests
MJ559: Dual operation 120 V 50/60 Hz mains (line) supply and
rechargeable battery. Six Ni Cad cells (e.g. AA, NEDA 15 NC)
Safety
The instruments meet the requirements for double insulation to
IEC 1010-1(1995), EN 61010 (1995) to installation Category II, 300 V
phase to earth (ground), 600 V installation Category I
Flash Test
6 kV a.c. r.m.s.
100
80
60
40
20
0
.01 .02
100V
.05
250V
.1
500V
.2
1kV
.5
TEST RESISTANCE MΩ
1
2
5
Insulation Resistance Testers
10
20
50
100
200
300 1k 2k ∞
MJ TESTERS