VPS420-R Fluke, VPS420-R Datasheet - Page 3

HIGH WORKING VOLTAGE PROBE, 100:1, RED & BLACK

VPS420-R

Manufacturer Part Number
VPS420-R
Description
HIGH WORKING VOLTAGE PROBE, 100:1, RED & BLACK
Manufacturer
Fluke
Type
High Voltage Prober
Datasheet

Specifications of VPS420-R

Test Probe Type
Scopemeter
Test Probe Functions
Voltage
Color
Red
Accessory Type
Voltage Probe Set
Equipment Type
Test Equipment
Measured Components
Voltages
Product
Accessories
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
Lead Free Status / RoHS Status
na
3
Built to with-
stand harsh
environments
with the highest
safety ratings
Rated all the way to CAT IV
ScopeMeter test tools are rugged solutions built
for industrial troubleshooting. The new Fluke
190 Series II are double-insulated floating
oscilloscopes safety rated for measurements in
CAT III 1000 V/CAT IV 600 V environments. The
two-channel Fluke 190C Series is rated CAT II
1000 V/CAT III 600 V.
Measure from mV to kV safely
Independent isolated inputs allow you to make
measurements in mixed circuits having different
ground references and reduces the risk of acci-
dental short circuits.
special differential probes and isolation trans-
formers can only reference measurements to
line power earth ground.
cation range from mV to kV, you’re ready for
anything from microelectronics to heavy-duty
medium voltage electrical applications.
The only IP-51 rated scopes on the
market
Rugged and shock-proof, ScopeMeter portable
oscilloscopes are built for harsh environments.
With its sealed case, it can endure dust, drips,
humidity and airborne pollutants. Every time
you reach for the scope you can be confident it
will work reliably.
Conventional bench oscilloscopes without
With standard probes that cover a wide appli-
Table 1. Overvoltage installation categories. IEC 61010 applies to low-voltage
(< 1000 V) test equipment.
Overvoltage
category
CAT IV
CAT III
CAT II
CAT I
In brief
Three-phase at
utility connection,
any outdoor
conductors
Three-phase
distribution,
including single-
phase commercial
lighting
Single-phase
receptacle
connected loads
Electronic
Examples
Refers to the “origin of installation, ” that
is, where low-voltage connection is made
to utility power
Electricity meters, primary overcurrent
protection equipment
Outside and service entrance, service
drop from pole to building, run between
meter and panel
Overhead line to detached building,
underground line to well pump
Equipment in fixed installations, such as
switchgear and polyphase motors
Bus and feeder in industrial plants
Feeders and short branch circuits,
distribution panel devices
Lighting systems in larger buildings
Appliance outlets with short connections
to service entrance
Appliance, portable tools, and other
household and similar loads
Outlet and long branch circuits
Protected electronic equipment
Equipment connected to (source) circuits
in which measures are taken to limit
transient overvoltages to an appropriately
low level
Any high-voltage, low-energy source
derived from a high-winding resistance
transformer, such as the high-voltage
section of a copier
Outlets at more than 10 meters (30 feet)
from CAT III source
Outlets at more that 20 meters (60 feet)
from CAT IV source