205-1-1-52-1-502 AIRPAX, 205-1-1-52-1-502 Datasheet - Page 17
205-1-1-52-1-502
Manufacturer Part Number
205-1-1-52-1-502
Description
Circuit Breaker Magnetic Circuit Protectors 1Pole 5A 2-Pin
Manufacturer
AIRPAX
Type
Magnetic Circuit Protectorsr
Datasheet
1.UPL11-1-61-403.pdf
(24 pages)
Specifications of 205-1-1-52-1-502
Current Rating
5 A
Number Of Poles
1
http://airpax.sensata.com/
Notes: DC units do not require series fusing.
277Vac: A circuit protector with this voltage rating is intended for 277Vac per pole single phase source only usage. (e.g.) 60 ampere units and 277/480Vac units require
a 2 x 4 inch interphase barrier for mulitpole units. If a two or three pole protector is marked 277Vac, all line terminals must be connected to the same phase, assuming
the 277 Vac is taken from line to neutral of a three phase 277/480Vac system.
Series and Shunt
Series Only
relay
Switch Only
205/295 - RATINgS
Configurations
0.050 - 50
0.050 - 100
0.050 - 60
0.050 - 50
0.050 - 20
0.050 - 50
0.050 - 50
21 - 50
0.050 - 20
0.050 - 30
0.050 - 30
0.050 - 50
0.050 - 50
0.050 - 50
0.050 - 50
50 amperes max. 65Vdc
100 amperes max. 32Vdc
50 amperes max. 250Vac (50/60Hz)
50 amperes max. 250Vac (400Hz)
Current Ratings (Amps)
65Vdc
65Vdc
120Vac (50/60Hz)
120Vac (50/60Hz)
277Vac (50/60Hz)
250Vac (50/60Hz)
120Vac (400Hz)
250Vac (400Hz)
250Vac (400Hz)
277/480Vac (50/60Hz)
277/480Vac (50/60Hz)
50Vdc
120Vac (50/60Hz)
120Vac (400Hz)
250Vac (50/60Hz-400Hz)
—
—
—
—
Maximum Voltage Ratings
APL/UPL, 205/295 Series - 205/295 Specifications
5000
3000
1000
5000
5000
5000
1500
1000
2100
5000
1500
—
—
—
—
—
—
—
—
Interrupting Capacity (Amps)
None
None
None
4X (125 max.)
4X
4X (125 max.)
None
None
None
4X (80A max.)
None
—
—
—
—
—
—
—
—
Series fuse