PT 2+1-S-48DC/FM Phoenix Contact, PT 2+1-S-48DC/FM Datasheet - Page 2

no-image

PT 2+1-S-48DC/FM

Manufacturer Part Number
PT 2+1-S-48DC/FM
Description
Manufacturer
Phoenix Contact
Datasheet

Specifications of PT 2+1-S-48DC/FM

Lead Free Status / RoHS Status
Compliant
PT 2+1-S-48DC/FM
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2817958
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Standards for air and creepage distances
Degree of protection
Design
Mounting type
Ambient temperature (operation)
Arrester can be tested with CHECKMASTER from
software version:
Direction of action
Width
Height
Length
Pitch unit
Protective circuit
IEC category
EN type
Nominal voltage U
Arrester rated voltage U
Arrester rated voltage U
Nominal current I
Operating effective current I
Ground conductor current I
Nominal discharge surge current I
Nominal discharge surge current I
Nominal discharge surge current I
PE)
Max. discharge surge current Imax (8/20) µs
Max. discharge surge current Imax (8/20) µs
maximum (L-N)
Max. discharge surge current Imax (8/20) µs
maximum (L-PE)
Combined surge U
Protection level U
N
P
N
OC
(L-N)
C
C
(L-PE)
PE
Order No.: 2817958
C
at U
C
n
n
n
(8/20) µs
(8/20) µs (L-N)
(8/20) µs (L-
DIN VDE 0110-1
IEC 60664-1: 1992-10
DIN VDE 0675-6
IEC 61643-1
IP20
DIN rail module, two-section, divisible
DIN rail: 35 mm
-40 °C ... 85 °C
From SW rev. 1.00
1L-N & N-PE
17.70 mm
65.50 mm
90.00 mm
1 Div.
III
T3
T3
48 V DC
60 V DC
60 V DC
26 A (at 30°C)
≤ 10 µA
≤ 10 mA
500 A
500 A
500 A
500 A
500 A
500 A
6 kV (for 12 Ω)
≤ 120 V
Dec 10, 2010
Page 2 / 6

Related parts for PT 2+1-S-48DC/FM