BB2-B0-26-640-521-C Carling Technologies, BB2-B0-26-640-521-C Datasheet - Page 2

Circuit Breakers 40A TWO POLE

BB2-B0-26-640-521-C

Manufacturer Part Number
BB2-B0-26-640-521-C
Description
Circuit Breakers 40A TWO POLE
Manufacturer
Carling Technologies
Series
Br
Datasheet

Specifications of BB2-B0-26-640-521-C

Product Type
Circuit Breakers
Current Rating
40 Amps
Voltage Rating
277 VoltsAC, 80 VoltsDC
Trip Time
10 s to 90 s
Mounting Style
Screw
Termination Style
Screw
Circuit Function
Series Trip (Current)
Color
White
Dielectric Strength
1500 V
Features
Control panels and marine equipment
Height
50.8 mm
Illuminated
No
Length
43.94 mm
Product
Hydraulic Magnetic Circuit Breakers
Width
39.62 mm
Number Of Poles
2 Poles
Actuator Type
Handle
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
58
B-Series – General Specifications
Notes for Table A:
1
2
3
Electrical
Table A:
Protector.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse (15A minimum) at no more than 4 times the rating of the protector.
Same as note 1, except that backup fuse is limited to 80A maximum.
2 pole protector required (with one pole per power line) for: 250/125 VAC, 125/250 VAC and 208Y/120 VAC Power Systems. 1 pole protector required for : 125 VAC, 1Ø Power System.
Lists UL Recognized & CSA Certified configurations and performance capabilities as a Component Supplementary
www.carlingtech.com