CB3-B0-34-615-121-D Carling Technologies, CB3-B0-34-615-121-D Datasheet - Page 3

Circuit Breakers 15 A 3 POLE

CB3-B0-34-615-121-D

Manufacturer Part Number
CB3-B0-34-615-121-D
Description
Circuit Breakers 15 A 3 POLE
Manufacturer
Carling Technologies
Type
Hydraulic/Magneticr

Specifications of CB3-B0-34-615-121-D

Product Type
Circuit Breakers
Actuator Type
Handle
Application
Higher amperage and voltage handling capability in a compact design
Brand/series
C Series
Current, Rating
15 A
Dimensions
2.475"Lx2.265"Wx2.5"H
Mounting Hole Size
0.156 "
Mounting Type
Panel
Number Of Poles
3
Resistance, Insulation
100 Megohms (Min.) @ 500 VDC
Standards
VDE Certified, UL Recognized, CSA Certified
Termination
Stud
Voltage, Rating
480 WYE/277 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
76
C-Series General Specifications
Notes for Table B:
1
2
Table B:
Electrical
Table C:
Component Supplementary Protector.
Notes for Table C:
1
2
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to
exceed 175 for 51 through 100 Amp rating.
UL recognized and CSA Accepted at 480V refers to 3 & 4 pole versions used in a 3Ø, wye connected circuit or 2-pole version connected with 2 poles breaking. 1Ø and backed up with series
fusing as stated above in note 1.
General Purpose ratings for UL/CSA only.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full load amps not to exceed 125A for 50 Amp or less rating and not to
exceed 175 for 51 through 100 Amp rating.
Lists UL Recognized and CSA Accepted configurations and performance capabilities as a Manual Motor Controller.
Lists UL Recognized, CSA Accepted , VDE and TUV Certified configurations and performance capabilities as a
www.carlingtech.com