FAN TUBEAXIAL 150X55MM 230VAC

W2S130-AA03-44

Manufacturer Part Number
W2S130-AA03-44
Description
FAN TUBEAXIAL 150X55MM 230VAC
Manufacturer
EBM-Papst Industries Inc
Series
W2S130r
Type
Roundr

Specifications of W2S130-AA03-44

Bearing Type
Ball
Voltage Rating
230VAC
Power (watts)
38W
Size / Dimension
Round - 150mm Dia x 55mm W
Termination
2 Terminals
Fan Type
Tubeaxial
Termination Style
53 dB(A)
Air Flow
223.6 CFM (6.33m³/min)
Weight
2.4 lbs (1.1kg)
Noise
53 dB(A)
External Depth
55mm
External Diameter
150mm
Current Type
AC
Supply Voltage
230VAC
Flow Rate
225CFM
Noise Rating
52dBA
Power Connection Type
Terminal
Diameter
150mm
Product
Fans
Brand/series
W2S130
Dimensions
5.91 x 2.17 "
Direction
Exhaust over Struts
Frequency
60 Hz
Noise Level
53 dBA
Power Rating
38
Power, Rating
38 W
Size
5.91 x 2.17 (150 x 55) In. (mm)
Temperature, Operating, Maximum
+70 °C
Voltage, Rating
230 VAC
Flow Rate - Imperial
225CFM
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Rpm
-
Static Pressure
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
W2S130AA0344

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
W2S130-AA03-44
Manufacturer:
EBM
Quantity:
2 000
Prerequisites
➜ Check whether the data on the type plate agree with the connection data.
➜ Before connecting the device, ensure that the mains supply voltage
➜ Only use cables designed for current according to
Residual current operated device
Voltage control
Frequency inverter
Motor protection
Connecting cables with terminals (applicable only to devices with terminal
connection)
4/5
matches the fan voltage.
the type plate.
Only all-current-sensitive RCD protective devices
(type A) are permissible. Like frequency inverters, RCD protective
devices cannot provide personal safety while operating the device.
With open loop speed control using transformers or electronic volt-
age regulators (e.g. phase angle control), excessive current may
occur.
In addition, noises can occur with phase control, depending on the
manner in which the device is installed.
Fit sinusoidal filters that work on all poles (live-live and live-earth)
between the frequency inverter and the motor for operation with
frequency inverters.
WARNING
Device without overheating protection
The device is delivered without any automatically functioning overhe-
ating protection. The device can become hot and burn.
➜ For the version without TOP, install an additional, suitable motor
(Applicable only to devices without off-board TOPs)
CAUTION
Electrical voltage
The device is a built-in component and features no electrically isolat-
ing switch.
➜ Connect the device only to circuits that can be switched off using
➜ When working on the device, you must switch off the sys-
(Applicable only to devices with off-board TOPs)
The motors are equipped with thermal overload protectors to protect
the devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect up the thermal overload protector correctly will
invalidate your right to claim damage for any defects. (Applicable
only to devices with off-board TOPs)
WARNING
Terminals and connections have voltage even in a unit that is
shut off
Electric shock
➜ Wait five minutes after disconnecting the voltage at all poles
protection switch.
an all-pole disconnecting switch.
tem/machine in which the device is installed and secure it from
being switched on again.
before touching the unit.
3.3 Checking the connections
➜ Ensure that the power is off.
➜ Secure it from being switched on again.
➜ Check the correct fit of the connecting cables.
3.4 Switching on the device
➜ Inspect the device for visible external damage and the proper function of the
➜ Apply the nominal voltage to the voltage supply.
3.5 Switching off the device
➜ Separate the device from the supply voltage.
protective features before switching it on.
WARNING
Electric voltage on cable gland
Electric shock
➜ Do not use plastic terminal boxes with metal cable glands.
WARNING
Hot motor housing
Fire hazard
➜ Ensure that no combustible or flammable materials are located
in the vicinity of the fan.