E2E-X5MY1-M4 Omron, E2E-X5MY1-M4 Datasheet - Page 5

Proximity Sensors PROX M12 AC NO UNSHI ELDED W/CO

E2E-X5MY1-M4

Manufacturer Part Number
E2E-X5MY1-M4
Description
Proximity Sensors PROX M12 AC NO UNSHI ELDED W/CO
Manufacturer
Omron
Type
Inductive Proximity Sensorr
Series
E2Er
Datasheets

Specifications of E2E-X5MY1-M4

Proximity Sensor Type
Inductive
Proximity Sensor Sensing Distance
5mm
Proximity Sensor Sensing Distance Range
2 to 7mm
Proximity Sensor Switching Mode
NO
Mounting
Panel
Operating Temp Range
-25C to 70C
Operating Temperature Classification
Commercial
Pin Count
4
Maximum Operating Temperature
+ 85 C
Mounting Style
Panel
Sensing Distance
5 mm
Minimum Operating Temperature
- 40 C
Features
NO
Sensor Type
Inductive
Sensing Object
Metallic
Response Frequency
25Hz
Material - Body
Nickel-Plated Brass
Shielding
Unshielded
Voltage - Supply
20 VAC ~ 264 VAC
Output Type
SCR-NO
Terminal Type
Connector
Package / Case
Cylinder, Threaded - M12
Lead Free Status / RoHS Status
Supplier Unconfirmed
Operation
J OUTPUT CIRCUITS
Sensors without Short-Circuit Protection (E2E-XjYj)
Sensors with Short-Circuit Protection (E2E-XjYj-US-53)
Short-Circuit Indication
The LED dims when the load is shorted and the load output immediately turns off and remains off until the short-circuit protection is reset.
Resetting Short-Circuit Protection
Before the short-circuit protection can be reset, the short must be repaired. We recommend turning the power off before repairing the
short. If this approach is taken, no further action is required to reset the short-circuit protection.
If the short must be repaired with power on, the following resetting steps are required:
For NO sensors, the target must be removed to reset the short-circuit protection.
For NC sensors, the target must be presented then removed to reset the short-circuit protection.
With Short-Circuit Protection
E2E-XjY1-53
NO
Load
Target
Output
Output
operation
indicator
E2E-XjYj-N AC 2-wire Models
Note: IEC colors are shown in parenthesis
E2E 2-WIRE AC
Main
circuit
Prox.
switch
main
circuit
Shorted
Normal
Present
Absent
ON
OFF
ON
OFF
Brown 1 (or 3)
Blue 2 (or 4)
Load
White (Brown)
Black (Blue)
Shorted
Normal
Present
Absent
ON
OFF
ON
OFF
E2E-XjY2-53
NC
Load
AC 2-wire Models
E2E-XjYj-N
Sensing
object
Red
indicator
Control
output
6
Not lit
OFF
ON
Yes
No
Lit
E2E 2-WIRE AC

Related parts for E2E-X5MY1-M4