TL-LP50 Omron, TL-LP50 Datasheet

no-image

TL-LP50

Manufacturer Part Number
TL-LP50
Description
Proximity Sensors DIE CAST AL 50M M NPN NO
Manufacturer
Omron
Type
Inductive Proximity Sensorr
Datasheet

Specifications of TL-LP50

Proximity Sensor Type
Inductive
Proximity Sensor Sensing Distance
50mm
Proximity Sensor Sensing Distance Range
50 to 300mm
Proximity Sensor Switching Mode
NO
Mounting
Screw
Operating Temp Range
-25C to 70C
Operating Temperature Classification
Commercial
Operating Supply Voltage (min)
10V
Operating Supply Voltage (typ)
12/15/18/24V
Operating Supply Voltage (max)
30V
Pin Count
3
Output Type
NPN
Maximum Operating Temperature
+ 70 C
Operating Supply Voltage
10 V to 30 V
Sensing Distance
50 mm
Minimum Operating Temperature
- 25 C
Features
NO
Lead Free Status / RoHS Status
Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
TL-LP50
Manufacturer:
OMRON
Quantity:
1 000
Part Number:
TL-LP50 1M
Manufacturer:
OMRON
Quantity:
500
Long-distance Model with a Sensing
distance of 50 mm.
Ordering Information
Note: Models with different frequencies are available. The model numbers are TL-L@50B.
Ratings and Specifications
* Full-wave rectified power supplies with a mean output of 24 VDC ±10% are available for the TL-LP50.
Column type
(flat-surface mounting)
Item
Sensing distance
Set distance
Differential travel
Sensing object
Standard sensing object
Response time
Power supply voltage (oper-
ating voltage range *)
Current consumption
Leakage current
Control
output
Indicators
Operation mode (with sens-
ing object approaching)
Ambient temperature
Ambient humidity
Temperature influence
Voltage influence
Insulation resistance
Dielectric strength
Vibration resistance
(destruction)
Shock resistance
(destruction)
Degree of protection
Connection method
Weight (packed state)
Materi-
als
Accessories
Long-distance Proximity Sensor
TL-LP/LY
Appearance
Be sure to read Safety Precautions on page 3.
Switching capacity
Residual voltage
Case
Sensing surface
http://www.ia.omron.com/
Model
Sensing distance
50 mm±10%
0 to 40 mm
10% max. of sensing distance
Ferrous metals (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on
the next page.)
Iron, 100 × 100 × 1 mm
15 ms max.
12 to 24 VDC (10 to 30 VDC), ripple (p-p) 10% max. 100 to 220 VAC (90 to 250 VAC), 50/60 Hz
10 mA max. (with no load)
NPN open collector with a maximum current of
200 mA at 30 VDC
3 V max. under a load current of 200 mA and a cable
length of 2 m
Operation indicator (red)
NO. Refer to the timing charts under I/O Circuit Diagrams on page 3 for details.
Operating/Storage: −25 to 70°C (with no icing or condensation)
Operating/Storage: 35% to 95% (with no condensation)
±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
±2% max. of sensing distance within a range of ±10% of rated power supply voltage
50 MΩ min. (at 500 VDC) between current-carrying parts and case
500 VAC (50/60 Hz) for 1min between current-
carrying parts and case
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
1,000m/s
IEC IP67
Pre-wired Models (Standard cable length: 1 m)
Approx. 1.4 kg
Die-cast aluminum
Polyester
Instruction sheet
2
50 mm
10 times each in X, Y, and Z directions
3-wire DC (normally open)
2-wire AC (normally open)
Output configuration
TL-LP50
---
(c)Copyright OMRON Corporation 2008 All Rights Reserved.
TL-LP50
TL-LY50
25 ms max.
Refer to Engineering Data on the next page.
10 to 200 mA
Refer to Engineering Data on the next page.
2,000 VAC (50/60 Hz) for 1 min between current-
carrying parts and case
Model
TL-LY50
---
1

Related parts for TL-LP50

TL-LP50 Summary of contents

Page 1

... Approx. 1.4 kg Case Die-cast aluminum Materi- als Sensing surface Polyester Accessories Instruction sheet * Full-wave rectified power supplies with a mean output of 24 VDC ±10% are available for the TL-LP50. http://www.ia.omron.com/ Output configuration 3-wire DC (normally open) 2-wire AC (normally open TL-LP50 --- 2 10 times each and Z directions (c)Copyright OMRON Corporation 2008 All Rights Reserved ...

Page 2

... TL-LY50 at 200 VAC 250 200 Operate ON 150 V mA 200 VAC 100 Reset OFF 100 500 Load current (mA) Column-type Sensing Object Diameter and Material vs. Sensing Distance TL-LP/- Reset Iron Operate 40 l > 120 D dia Reset Brass Operate 120 140 External diameter D dia. (mm) (c)Copyright OMRON Corporation 2008 All Rights Reserved ...

Page 3

... R5 18.5 75 *1. Vinyl cabtire cable: TL-LP50: 9.4-dia. vinyl-insulated round cable with 3 conductors (Conductor cross section: 0.75 mm TL-LY50: 9.0-dia. vinyl-insulated round cable with 2 conductors (Conductor cross section: 0.75 mm *2. Remove the hexagon nut if a PF1/2 cable protective tube is applied. (c)Copyright OMRON Corporation 2008 All Rights Reserved. ...

Page 4

... Be sure that the power supply polarity and oth- er wiring is correct. Incorrect wiring may cause explosion or burning. Connection without a Load If the power supply is connected directly with- out a load, the internal elements may explode or burn. Be sure to insert a load when connect- ing the power supply. ...

Page 5

... Conduits, ducts, pre-wired, terminal wiring, ease of main- tenance and inspection mT* max. Do not use the Sensor at a level higher than 20 mT. Life: Power-ON time/frequency of use (c)Copyright OMRON Corporation 2008 All Rights Reserved. Peripheral metal Sensing distance Material, distance Fluctuation in transit point, al- to Sensor, orien- lowable error, etc ...

Page 6

... Sensing Object Material The sensing distance varies greatly depending on the material of the sensing object. Study the engineering data for the influence of sensing object material and size and select a distance with sufficient leeway. • In general, if the Example: E2-X10D@ sensing object is a non- ...

Page 7

... OFF It is recommend that leeway be included in the actual values used. For 12 VDC, use 15 kΩ or less and 450 mW or higher, and for 24 VDC, use 30 kΩ or less and 0 higher. (c)Copyright OMRON Corporation 2008 All Rights Reserved. AC power supply voltage Vs 2 (mW) ...

Page 8

... Loads with Large Inrush Current Loads, such as lamps or motors, that cause a large inrush weaken or damage the switching element. In this situation, use a relay. * E2K, TL-N@ higher ●Mounting Mounting the Sensor When mounting a Sensor, do not tap it with a hammer or otherwise subject it to excessive shock. This will weaken water resistance and may damage the Sensor ...

Page 9

... A parallel connection can be used if A and B will not be operated simulta- neously and there is no need to hold the load. The leakage current, however, Load will be n times the value for each Sensor and reset failures will frequently oc- cur. ("n" is the number of Proximity Sensors and B will be operated simultaneously and the load is held, a parallel con- nection is not possible ...

Page 10

... The residual voltage of the E2E-XD-M1J 3-Wire Sensors Operation can be reversed with the signal input switch on the S3D2. (c)Copyright OMRON Corporation 2008 All Rights Reserved. Description Example: A maximum of two Sensors can be used when an MY (24-VDC) Relay is used for the load ...

Page 11

... Disassembly and Repair Do not under any circumstances attempt to disassemble or repair the product. Quick Failure Check You can conveniently check for failures by connecting the E39-VA Handy Checker to check the operation of the Sensor. http://www.ia.omron.com/ Proximity Sensors Technical Guide (c)Copyright OMRON Corporation 2008 All Rights Reserved. ...

Page 12

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specifi ed) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...