ACA5-20RM-5-AC4-RL-C Murata Power Solutions Inc, ACA5-20RM-5-AC4-RL-C Datasheet - Page 2

AMMETER AC 200A 220VAC RED

ACA5-20RM-5-AC4-RL-C

Manufacturer Part Number
ACA5-20RM-5-AC4-RL-C
Description
AMMETER AC 200A 220VAC RED
Manufacturer
Murata Power Solutions Inc
Series
ACA5-20RMr
Type
Ammeterr
Datasheet

Specifications of ACA5-20RM-5-AC4-RL-C

Display Type
LED
Measuring Range
0 ~ 199.9A
Display Style
Red Characters, Black Background
Display Digits
3.5
Display Digits - Height
0.370" (9.40mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
170 ~ 264VAC
Dimensions
53.34 mm L x 35.56 mm W x 18.54 mm H
Mounting Style
Panel
Primary Voltage Rating
170 V to 264 V
Secondary Current Rating
199.9 A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Display Face Size
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
811-1977
Performance/Functional Specifi cations
Typical at T
Full-Scale Primary Current ➀
All Models
Overcurrent Rating ➁
Display Readings with 5A Flowing through the Ammeter’s Current Transformer
Model Number
ACA5-20RM-3-ACX-RL
ACA5-20RM-5-ACX-RL
ACA5-20RM-9-ACX-RL
Performance
Sampling Rate
Accuracy ➂
Input Frequency Range
Measurement Type
Temperature Drift (0 to 60 °C)
Zero-Current Reading (within 30 sec.)
Breakdown Voltage
Power Supply Voltage
ACA5-20RM-X-AC3-RL
ACA5-20RM-X-AC4-RL
Power Supply Current ➃
ACA5-20RM-X-AC3-RL
ACA5-20RM-X-AC4-RL
Power Supply Terminal Block (all models)
Wire Size
Insulation Strip Length
Screw Tightening Torque
Rated Voltage
Display
Display Type and Size
Overrange Indication
Display Reading/Decimal Point
Physical/Environmental
Operating Temperature
Storage Temperature
Humidity (non-condensing)
Dimensions
Weight
All models
A
= +25°C, unless otherwise noted.
–001
2000
Min.
170
–40
3½ Digit Red LED, 0.37”/9.4mm High
rms Responding, Crest Factors of 1-5
85
0
1.5 x Rated full-scale rms current
Model dependent, see page 4 & 5
1.1 Ounces (31 grams) nominal
±0.4%FS ±3 Counts with 60Hz
16-22AWG, Solid or stranded
3.6 pounds-inches (0.4Nm)
“Display Readings” above
2.5 Samples per second
47–63
±0.2
Typ.
Model dependent; see
000
120
220
30
30
Display Reading
Sine-Wave Input
0.250 inches
“1___”
310Vac
Max.
100.0
199.9
±0.4
+60
+75
001
140
264
5.0
500
50
50
85
www.murata-ps.com/dpm
Vac/47-63Hz
Vac/47-63Hz
mA/47-63Hz
mA/47-63Hz
rms Amps
Cnts/°C
Units
Cnts
Vdc
Hz
°C
°C
%
➀ The specifi ed full-scale current is the ac current circulating through the meter’s
➁ The overcurrent rating of 1.5 times the rated full-scale current is a continuous
➂ Specifi ed accuracy applies to inputs with crest factors (CF) up to 2.0, where CF
➃ All specifi ed maximum power supply currents are steady state; larger surge
TECHNICAL NOTES
ACA5-20RM-3-AC3-RL-C
ACA5-20RM-3-AC4-RL-C
ACA5-20RM-5-AC3-RL-C
ACA5-20RM-5-AC4-RL-C
ACA5-20RM-9-AC3-RL-C
ACA5-20RM-9-AC4-RL-C
Accessory Current Transformers for above*:
7020-01038-0
7020-01040-0
39-3681409
* See data sheet titled “Current Transformers” at www.murata-ps.com for more
information
1. Measurement Type: ACA5-20RM ac ammeters employ a true rms
2. Calibration: Periodic recalibration of ACA5-20RM ammeters is
built-in 5A current transformer’s primary circuit L1 (i.e., the external current
transformer’s 0-5A output current).
rms rating and applies to the current passing through the built in current trans-
former (CT). Accuracy is only guaranteed up to the rated full-scale CT current of
5Arms.
= Vpeak/Vrms. Crest factors of 2 to 5 introduce an additional error of ±3% of full
scale. Ammeters are calibrated with a 5.00Arms/60Hz current fl owing through
the ammeter’s built-in 5A CT.
currents can occur at initial turn-on.
Ordering Information
IMPORTANT! To ensure safe and reliable operation, ACA5-20RM
ammeters must be installed and serviced by qualifi ed technical
personnel. Contact Murata Power Solutions if there is any doubt
regarding ammeter installation and/or operation.
input circuit to measure the output of external 5A current transform-
ers. Stated accuracy specifi cations are measured using a sine-wave
current at, or close to, the full-scale input range, at nominal line
frequency of 60Hz.
not required under normal, indoor operating environments. If user
calibration is necessary, it should be performed by qualifi ed technical
personnel. Calibration is performed with potentially lethal voltages
applied to the ACA5-20RM and its associated wiring, with 5.0 amps
fl owing through the ammeter’s built-in toroid sensor. A plastic,
fully-insulated adjusting tool must be used to access the calibration
potentiometer located on the back of the meter (see Mechanical
Specifi cations). Contact MPS if additional information is required
regarding calibration, setup, or any other technical issue pertaining to
ACA5-20RM ammeters.
True-rms-AC Ammeters with 5A CT Inputs
ACA5-20RM Series
26 Jan 2011 MPM_ACA5-20RM.A04 Page 2 of 5
100.0A Range, 85-140Vac power
100.0A Range, 170-264Vac power
199.9A Range, 85-140Vac power
199.9A Range170-264Vac power
500A Range, 85-140Vac power
500A Range, 170-264Vac power
100A Current Transformer, RoHS compliant
200A Current Transformer, RoHS compliant
500A Current Transformer, not RoHS compliant
email: sales@murata-ps.com