PAXLPV00 Red Lion Controls, PAXLPV00 Datasheet - Page 8

METER PROCESS VOLT 3 1/2-DIGIT

PAXLPV00

Manufacturer Part Number
PAXLPV00
Description
METER PROCESS VOLT 3 1/2-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Voltmeterr
Datasheets

Specifications of PAXLPV00

Measuring Range
0 ~ 25 VDC
Display Style
Red Characters, Black Background
Display Type
LED
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
3.5
Display Digits - Height
0.560" (14.22mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Screw Terminals
Voltage - Supply
85 ~ 250VAC
No. Of Digits / Alpha
3-1/2
Meter Function
DC Process
Meter Range
± 0V To ± 25V
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +60°C
Supply Voltage Ac, Min
85V
Accuracy
±0.05% %
Common Mode Rejection Ratio
100 dB
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Function
Voltage
Number Of Digits
3-1/2
Primary Type
Electronic
Range, Measurement
±25 VDC
Response Time
1 sec.
Temperature, Operating
0 to 60 °C
Voltage, Input
±25 VDC
Voltage, Supply
85 to 250 VAC
Weight
0.65 lbs.
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
NA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
na, Contains lead / RoHS non-compliant
Other names
RLC113
Red Lion Controls
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Example 1 (± Display):
ADJUSTMENTS
Example 2 (Positive Offset):
ADJUSTMENTS
6.0 A
output (-15 @ 1 V, +15 @ 6 V)
READOUT SPAN (Rs) = +1500 - (-1500) = 3000
SWING VOLTAGE (Vs) = 6 V (max) - 1 V (min) = 5 V
SPAN PER VOLT (Rs/Vs) = 3000 / 5 V = 600
Note: Since the display readout is limited to 1999 numerical indication, the
V @ 40 GPM and 5 V @ 650 GPM.
READOUT SPAN (Rs) = 650 - 40 = 610
SWING VOLTAGE (Vs) = 5 V (max) - 0 V (min) = 5 V
SPAN PER VOLT (Rs/Vs) = 610 / 5 V = 122
Check min. and max. extremes and tweak
Set offset to readout 40 @ 0 V per Step 7.
Check the readout @ max. (5 V) and min.
Steps 1 to 4 of the calibration steps.
adjustments per Steps 5 and 6 to get a
readout of +1500 @ 2.5 V (SPAN PER
VOLT = 600).
reading of -1500 @ 1 V.
if required to get desired readout @ 1 V
and 6 V per step 8. Set D.P. switch S2
and replace unit in case.
Null the unit per Steps 1 to 4 of the
calibration steps.
Set the coarse and fine span adjustments
to get a readout of 610 @ 5 V (SPAN PER
VOLT = 122) per Steps 5 and 6.
(0 V) and fine tune (tweak) as required
per Step 8.
Null the unit to zero readout @ 0 V per
Apply (-) offset per Step 7 to get a
Set transfer curve slope with span
A differential pressure transducer has a range of ±15 PSI with a 1-6 V
full READOUT SPAN of 3000 cannot be obtained during zero based span
adjustment. However, dividing both the READOUT SPAN and SWING
VOLTAGE by two, i.e. 1500 readout @ 2.5 V, allows the span adjustment
to be made for the proper transfer curve slope.
PAXLPV is to be calibrated to match a flow transducer whose output is 0
PPLICATIONS
NL - 3821 AD Amersfoort
Fax +31 (0) 334 893 793
Tel +31 (0) 334 723 225
Red Lion Controls BV
Printerweg 10
Example 3 (Negative Slope):
ADJUSTMENTS
when the tank is empty. The PAXLPV is to read out 100.0 when the tank is
full and zero when the tank is empty.
READOUT SPAN (Rs) = 1000 - 0 = 1000
SWING VOLTAGE (Vs) = 1 V (max) - 11 V (min) = -10 V
SPAN PER VOLT (Rs/Vs) = 1000 / -10 V = -100
In this case, the signal voltage is reversed [Term. 3 (+) with respect to Term.
4 (-)] causing the readout to go “down” (increasingly negative) as the
negative voltage increases (hence, the negative (-) SPAN PER VOLT).
Set the slope of the transfer curve with the
Move the transfer curve up by applying (+)
calibration steps.
span adjustments to get a readout of -1000
@
-100) per Steps 5 and 6.
offset per Step 7 until readout is +1000 @
-1 V.
readout @ -11 V and +1000 @ -1 V. Set
D.P. switch S1 ON and replace unit in case.
Null the unit per Steps 1 to 4 of the
Check extreme readings per Step 8 0
A liquid level sensor puts out 1 V when a storage tank is full and 11 V
-10V
(SPAN
PER
VOLT
=
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Fax +86 21 6113-3683
Tel +86 21 6113-3688
Unit 101, XinAn Plaza
Red Lion Controls AP