SDV-FM7 AC200/220 Omron, SDV-FM7 AC200/220 Datasheet - Page 11

no-image

SDV-FM7 AC200/220

Manufacturer Part Number
SDV-FM7 AC200/220
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheets

Specifications of SDV-FM7 AC200/220

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Current Reverse-phase Detection Models
Specifications
Other features, such as 100% overcurrent capacity and flush mounting are also available. See Model Number Legend on page 8 for details.
Resetting
method
Manual
Automatic 100/110/120 VAC K2CM-1LSA K2CM-1LA K2CM-1MA K2CM-1HA K2CM-Q1LSA K2CM-Q1LA K2CM-Q1MA K2CM-Q1HA
Supply voltage of motor circuit
Supply voltage of control circuit
Insulation breakdown of output
contact
Operating voltage/current of output
contact (pf = 0.4 when breaking
contact)
Contact form of output contact
Operating current range of input
circuit
Operating voltage range of control
circuit
Operating frequency range of control
circuit
Power consumption
Overcurrent function operating value 115 10% of the setting value
Overcurrent function operating time
setting range
Ratings
100/110/120 VAC K2CM-1LS
200/220/240 VAC K2CM-2LS
400/440 VAC
200/220/240 VAC K2CM-2LSA K2CM-2LA K2CM-2MA K2CM-2HA K2CM-Q2LSA K2CM-Q2LA K2CM-Q2MA K2CM-Q2HA
400/440 VAC
Current setting
specification
Operating
voltage
range
Time
---
---
2 to 8 A
200/220, 400/440 VAC, 50/60 Hz
100/110/120, 200/220/240, 400/440 VAC, 50/60 Hz
500 VAC
NO contact: 120 VAC/2 A, 240 VAC/1 A, 440 VAC/0.5 A, 110 VDC/0.2 A, 220 VDC/0.1 A
NC contact: 120 VAC/5 A, 240 VAC/2 A, 440 VAC/1 A, 110 VDC/0.2 A, 220 VDC/0.1 A
Current reverse-phase detection models: SPST-NO + SPST-NC
Voltage reverse-phase detection models: SPDT
2 to 160 A (Number of passes: 1)
85% to 110% of rated voltage, but operates normally at 50% of open-phase supply voltage
95% to 105% of rated frequency
Approx. 3 VA (in standby state); 5 VA (in operating state)
Inverse Type
Inverse time both at starting and during operation
• Time setting value (varies between 2 and 40 s) at 600% overload
• Time setting value
Instantaneous Type
Fixed time at starting (start-up lock)
• Time setting value (varies between 2 and 40 s) at 140% overload and starting
Instantaneous during operation: 0.5 s max. (when current is increased from 100 to 140% of the set
current value)
K2CM-1L
K2CM-2L
K2CM-4L
K2CM-4LA K2CM-4MA K2CM-4HA ---
8 to 26 A
Inverse type
K2CM-1M
K2CM-2M
K2CM-4M
20 to 65 A 50 to 160 A
3 at 200% overload
K2CM-1H
K2CM-2H
K2CM-4H
K2CM-Q1LS
K2CM-Q2LS
---
2 to 8 A
Motor Protective Relay
K2CM-Q1L
K2CM-Q2L
K2CM-Q4L
K2CM-Q4LA K2CM-Q4MA K2CM-Q4HA
8 to 26 A
Instantaneous type
K2CM-Q1M
K2CM-Q2M
K2CM-Q4M
20 to 65 A
K2CM
K2CM-Q1H
K2CM-Q2H
K2CM-Q4H
50 to 160 A
9