2885809 Phoenix Contact, 2885809 Datasheet - Page 2

I/O Modules EMD-FL-PF-400

2885809

Manufacturer Part Number
2885809
Description
I/O Modules EMD-FL-PF-400
Manufacturer
Phoenix Contact
Datasheet

Specifications of 2885809

Control Voltage Range
250 VAC
Load Voltage Rating
24 V to 240 V
Case Color
Green
Relay Type
Electronic Monitoring Relay
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
EMD-FL-PF-400
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2885809
The operating states are indicated using colored LEDs, errors that may occur can be sent to a control system via a
floating contact or can shut down a part of the system. Some device versions are equipped with startup and response
delays in order to briefly tolerate measured values outside the set monitoring range.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Technical data
Input data
Nominal input voltage U
Input voltage range
Input current range
Overload capacity
Maximum temperature coefficient
Function
Setting range for response delay
Setting range for starting delay
Basic accuracy
Setting accuracy
Repeat accuracy
Recovery time
Contact side
Contact type
Maximum switching voltage
Interrupting rating (ohmic load) max.
Output fuse
Power supply
Supply voltage range
General data
Width
Height
Depth
Mechanical service life
Operating mode
Order No.: 2885809
N
(3 N ~ 415/240 V)
1(N) ~ 40 V AC ... 415 V AC
3 (N) ~ 40 V AC ... 415 V AC
0.5 A ... 10 A (Connection terminal blocks: L1i and L1k)
12 A permanent
≤ 0.1 %/K
Underload, overload, Window
0.1 s ... 40 s
1 s ... 100 s
± 5 % (At cos φ = 0.8)
≤ 5 % (At cos φ = 0.8)
± 1.8 %
500 ms
2 floating PDT contacts
250 V AC (in acc. with IEC 60664-1)
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
5 A (fast-blow)
24 V AC ... 240 V AC -15 % ... +10 %
24 V DC ... 240 V DC -20 % ... +25 %
22.5 mm
90 mm
113 mm
Approx. 2 x 10
100% operating factor
7
cycles
Jun 3, 2011
Page 2 / 5