QS982A Converter Card Lineage Power, QS982A Converter Card Datasheet - Page 2

no-image

QS982A Converter Card

Manufacturer Part Number
QS982A Converter Card
Description
Linear & Switching Power Supplies -48V-+/-190V 2x100VA Convert/Limiter card
Manufacturer
Lineage Power
Datasheet

Specifications of QS982A Converter Card

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
108996641
Data Sheet
June 2009
Dual Input Converter Card Specifications
2
Input
Input Voltage Range
Maximum Input Current at Vin=40.0 Vdc
Maximum Inrush Current
Input Conducted Noise Spectrum
Input Protection
Output
Output Voltage Setpoint
Output Voltage Regulation
Output Voltage Ripple
Output Conducted Noise Spectrum
Output Protection
Output Power
Output Current Overcurrent limit
Output Overvoltage Limit
Environmental
Efficiency
Operating Temperature Range
Operating Humidity Range
Storage Temperature Range
Storage Humidity Range
Indicators
Safety / Standards Compliance
Electrical safety
EMC
Environment
Isolation
QS982A
RMS (5 Hz to 20 MHz)
Peak-Peak (5 Hz to 20 MHz)
QS982A
QS982A
-40 Vdc to -59 Vdc
7A
7A
< GR-1089 limits (10 kHz to 30 MHz)
Fuses, diode reverse input polarity
±188.3 Vdc to ±192.1 Vdc
±1.0%
500 mV
2.5V
< GR-1089 limits (10 kHz to 30 MHz)
Over/Under Voltage Shutdown, Overcurrent Shutdown,
Ground Fault Shutdown
95 VA/ channel minimum; 190 VA/card
0.251A min (each circuit)
±200 Vdc max
85% (typical)
-40 to +65 °C (-40 to +149 °F) with 175 lfm airflow
5% to 95% RH non-condensing
-40 to +85 °C (-40 to +185 °F)
0% to 99% RH non-condensing
OK and FLT for each circuit
UL60950-1, UL60950-21
FCC-Class A, GR-1089
NEBS Level 3
1500V (-48 V input to ±190V output)
CPS3200U Upstream System
Telephone Power for Video
Lineage Power

Related parts for QS982A Converter Card