E2K-C25MY2 Omron Automation, E2K-C25MY2 Datasheet - Page 6

no-image

E2K-C25MY2

Manufacturer Part Number
E2K-C25MY2
Description
Sensor; Capacitive Sensing Mode; 1.34 in. Dia.; NC; 0.12 to 0.98 in.; 10 Hz
Manufacturer
Omron Automation
Type
Capacitiver
Datasheet

Specifications of E2K-C25MY2

Body Style
Cylindrical
Current, Rating
1 mA (Max.) @ 100 VAC, 2 mA (Max.) @ 200 VAC
Current, Switching
200 mA
Frequency, Switching
10 Hz
Function
Proximity
Indicator
Output Operation (Red LED)
Ip Rating
IP66
Material, Housing
ABS⁄PC
Mounting Type
Bracket
Output
NC
Primary Type
Proximity
Range, Measurement
0.12-0.98 In.
Standards
UL Listed, CSA Certified
Technology
Capacitive
Temperature, Ambient, Maximum
+70 °C
Temperature, Ambient, Minimum
-25 °C
Termination
2-Wire Cable
Voltage, Supply
220 VAC
Voltage, Switching
250 VAC
Supply Voltage Range
10-40 VDC or 90-250 VAC, 50/60 Hz
Load Rating
200 mA (DC) or 5-200 mA (AC)
Approvals
CE, UL, CSA (Model Dependant)
Lead Free Status / Rohs Status
RoHS Compliant part

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
E2K-C25MY2
Manufacturer:
OMRON
Quantity:
463
Dimensions
Sensors
Accessories (Order Separately)
Mounting Bracket (Accessory)
Y92E-A34
Note: Provided with the product.
Material: Polyacetal
51
34 dia.
30
34 dia.
E2K-C25M@@
E2K-C20M@@
5.2
14
20
R2.6
54.4
57.6
45
43
42
45
C Models: 5.5-dia. vinyl-insulated round cable with 3 conductors
T Models: 5.5-dia. vinyl-insulated round cable with 2 conductors
82
81
6.3
Two, M4 Sensor clamping screws
Cable clamp
Two elliptic holes for bracket mounting
Sensor mounting hole
Two, 5.5-dia. mounting holes*
* The holes are not drilled
15
completely through. Drill through
the holes before using them.
(Conductor cross section: 0.5 mm
diameter: 1.5 mm), Standard length: 2 m
(Conductor cross section: 0.5 mm
diameter: 1.5 mm), Standard length: 2 m
23.5
2
35
E Models: 6-dia. vinyl-insulated round cable
Y Models: 6-dia. vinyl-insulated round cable
7
18
9
Cap
13
with 3 conductors (Conductor cross
section: 0.5 mm
1.9 mm), Standard length: 2 m
with 2 conductors (Conductor cross
section: 0.5 mm
1.9 mm), Standard length: 2 m
Operation indicator (yellow)
2
2
With Mounting Bracket Attached
, Insulator
, Insulator
30
Screw hole for sensitivity
adjustment
2
2
, Insulator diameter:
, Insulator diameter:
35
-
+
* E Models: Detection indicator (red)
Y Models: Operation indicator (red)
Indicator*
Sensitivity adjuster
E2K
6
E2K-C
(Unit: mm)