H12D4890 Crydom Company, H12D4890 Datasheet
H12D4890
Manufacturer Part Number
H12D4890
Description
Relay; SSR; Zero-Switching; Cur-Rtg 90A; Ctrl-V 4-32DC; Vol-Rtg 48-530AC; Pnl-Mnt
Manufacturer
Crydom Company
Datasheet
1.H12D4850.pdf
(3 pages)
Specifications of H12D4890
Brand/series
H12D Series
Current, Leakage, Off-state
10 mA (RMS)
Current, Rating
90 A
Current, Surge
1200 Apk (Max.) @ 16.6 ms
Dielectric Strength
4000 V (RMS) @ 50⁄60 Hz
Dimensions
2.30 in. L x 1.80 in. W x 0.78 in. H
Function
Zero-Switching
Mounting Type
Panel
Number Of Pins
4
Relay Type
Solid State
Resistance, Thermal, Junction To Case
0.28 °C⁄W
Standards
UL, CSA, VDE, CE
Temperature, Ambient, Maximum
80 °C
Temperature, Ambient, Minimum
-40 °C
Termination
Saddle Clamp
Transient Overvoltage
1200 Vpk
Voltage, Control
32 VDC
Voltage, Rating
530 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
Related parts for H12D4890
H12D4890 Summary of contents
Page 1
...
Page 2
... VAC. All models come with 1200 Volts blocking and are available with either input (coil) control. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability. H12D48125 H12D4875 H12D4890 48-530 48-530 150 150 150 ...
Page 3
Available Options F Faston Terminals. ( Amp Models) Example: H12D4850F Input Status LED. G Agencies Approval Pending Example: H12D4850G Note: Control Voltage Range 5.5-32 Vdc P Internal Overvoltage Protection. Relay Will Self Trigger Between 900-1200Vpk. Not Suitable For ...