E5GN-R1T AC100-240 Omron Automation, E5GN-R1T AC100-240 Datasheet - Page 14

no-image

E5GN-R1T AC100-240

Manufacturer Part Number
E5GN-R1T AC100-240
Description
Controller, Digital Temp, 48x24mm, Relay Out, Thermoc In, 100 to 240 VAC, 1 Alar
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5GN-R1T AC100-240

Brand/series
E5GN Series
Dimensions
48mmWx35mmHx101mmD
Mounting Type
Panel
Standards
UL, cULus, CSA
Termination
Screw Terminals
Voltage, Supply
100 to 240 VAC
External Connections
E5GN
Wiring
E5GN
Models with Screw Terminal Blocks (M3 Screws)
Relay output
Voltage output (for driving SSR)
Current output
• A voltage output (control output, for driving SSR) is not electrically
Relay outputs
250 VAC, 2 A (resistive load)
12 VDC, 21 mA
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
250 VAC, 2 A (resistive load)
insulated from the internal circuits. When using a grounding
thermocouple, do not connect any of the control output terminals to
Auxiliary outputs 1 and 2
Control output 1
Auxiliary output 2
connection screws
13
Auxiliary
output 2
14
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
M3 Screw Terminal Blocks
The E5@N-@@@T@ is set for a K thermocouple
(input type of 5) by default. If a difference sensor is
used, an input error (s.err) will occur. Check the
setting of the input type parameter.
RS-232C
communications
RS-485
communications
Crimp terminal shape: Forked or round
Tightening torque for all terminals: 0.5 N
Event input
CT input
B (+)
5.8 mm max.
5.8 mm max.
Input power
SD
7
1
supply
CT
A (−)
RD
8
2
EV1
m
DO NOT
USE
+ Control
DO NOT
USE
SG
EV2
9
3
output 1
DO NOT
USE
+
10
4
Controllers
E5GN-@-C
Models with Screwless Clamp Terminal Blocks
A
mA
ground. (If the control output terminals are connected to ground,
errors will occur in the measured temperature values as a result of
leakage current.)
11
5
Models with Screw
Terminal Blocks
Auxiliary
output 1
Terminal Arrangement
B
1
7
V
DO NOT
USE
2
8
12
6
B
+
+
9 10 11 12
3
Universal TC/Pt input
Analog input
4
5
6
A heater burnout alarm, heater short
alarm, heater overcurrent alarm, or
input error is sent to the output to
which the alarm 1 function is assigned.
Models with Screwless Clamp Terminal Blocks
Wire stripping: 10 mm
Ferrules: 8 to 12 mm
Models with Screwless
Clamp Terminal Blocks
10 mm
7
1
8
2
9 10 11 12
3
0.8 to 1.4 mm
4
5
E5GN
8 to 12 mm
6
14