9070T50D1 TELEMECANIQUE, 9070T50D1 Datasheet

no-image

9070T50D1

Manufacturer Part Number
9070T50D1
Description
Transformer; 50 VA; 220/440, 230/460, 240/480 V; 110, 115, 120 V; 50/60 Hz
Manufacturer
TELEMECANIQUE
Type
Controlr
Datasheet

Specifications of 9070T50D1

Capacity
50 VA
Configuration
Bobbin
Dimensions
3"W×2.58"H×3.09"D
Frequency
50/60 Hz
Mounting Type
Panel/Chassis
Number Of Outlets
1
Phase
1
Power, Rating
50 VA
Standards
UL, cUL, CSA, CE, TUV
Temperature, Operating
+55 °C
Termination
Screw Terminals
Voltage, Primary
240/480, 230/460, 220/440 VAC
Voltage, Secondary
120/115/110 VAC
Weight
2.5 lbs.
Product Data Sheet
Technical Characteristics
Shipping and Ordering
As standar
Application
Approvals
Height
Depth
Catalog Reference Number
Width
Insulation Temperature
Temperature Rise
Type
Primary
Phase
Secondary
Mounting Type
Enclosure Type
Rating
Terminal Type
Winding Material
Category
Discount Schedule
Article Number
Package Quantity
Weight
Availability Code
Returnability
© 2008 Schneider Electric. All rights reserved.
9070T50D1
Industrial Control Transformer , 50VA
Specifically designed to handle high inrush associated with contactors and relays for
applications such as conveyor systems, paint lines, punch presses or overhead cranes
UL Listed File Number: E61239 - CSA Certified File Number: LR37055 Guide: 184-N-90 -
CE Marked
2.58 Inches
3.09 Inches
9070CT9901
3.00 Inches
105 Degrees C
55 Degrees C
T
240x480V or 230x460V or 220x440V
1-Phase
120V or 115V or 110V
Panel
Open
50VA
Screw Clamp
Copper
16200 - Transformers, Industrial Control, 50 - 200 va, Type T
CP8
785901904632
1
2.53 lbs.
S
Y
1

Related parts for 9070T50D1

9070T50D1 Summary of contents

Page 1

... Availability Code Returnability As standar © 2008 Schneider Electric. All rights reserved. 9070T50D1 Industrial Control Transformer , 50VA Specifically designed to handle high inrush associated with contactors and relays for applications such as conveyor systems, paint lines, punch presses or overhead cranes UL Listed File Number: E61239 - CSA Certified File Number: LR37055 Guide: 184-N- Marked 2 ...

Page 2

... OEMs. Since the fuse blocks are pre-wired and mounted on top of the transformer, the Type TF and EOF transformers have the same footprint as the Type T and Type EO units, respectively. This design frees up space normally used for separate fuse blocks We also have an extensive fuse block offering for custom applications ...

Page 3

... Because of different overload criteria in the CE specification, 250–1000 Schneider Elecric dual rates these transformers for UL VA, cUL VA, CSA VA, NOM VA and CE VA ratings (see “Type T VA Ratings” table). Because they are widely used with control circuit panels, ICTs are also required to 1500– ...

Page 4

... Primary Secondary 220/230/240 V:Connect to H1 and H4 220 x 440 110 D1 230 x 460 115 240 x 480 120 440/460/480 V:Connect to H1 and H4 Dimensions VA Catalog Figure Number 9070T25D1 9070T50D1 9070T75D1 1 100 100 9070T100D1 1 150 150 9070T150D1 1 200 200 9070T200D1 1 250 160 9070T250D1 2 300 200 9070T300D1 ...

Page 5

... 3000 2000 9070T3000D15 3.38 (85.8) 3.34 (84.8) 3.8 5000 3000 9070T5000D15 3.75 (95.3) 3.59 (91.2) 5.5 3.75 (95.3) 3.59 (91.2) 5 9070T50D12 3.75 (95.3) 5.25 (133.4) 7 9070T75D12 4.50 (114.3) 4.70 (119.4) 8.5 100 100 9070T100D12 4.50 (114.3) 5.09 (129.3) 10.5 150 150 9070T150D12 4 ...