Description
Control Unit; 14 Points (Control) Max. Number of Expansion I/O Points; Relay; 8
Manufacturer
Panasonic Electric Works
Type
Temperature/Timerr
Datasheet

Specifications of AFPE224300

Brand/series
FP-e Series
Communication
RS-232
Current, Input
4.3 mA
Dimensions
48mmW×48mmH×77.5mmD
Enclosure Rating
IP66
Input Type
Voltage
Ip Rating
IP66
Max. Number Of Expansion I/o Points
14 Points (Control)
Memory
EEPROM
Memory Type
EEPROM
Mounting Type
Panel
Number Of Inputs
8
Number Of Outputs
6
Output Type
Digital/Relay
Primary Type
Controller
Programmable With
Communication port RS232C
Special Features
Serial Communications
Voltage, Supply
24 VDC
Compact And Space-saving
48 mm (W) × 48 mm (H) × 70 mm (D)
Lead Free Status / Rohs Status
RoHS Compliant part
FP-e Series
Technical data
6
Note 1)
Number of input
Insulation method
Rated input voltage
Operating voltage range
Rated input current
Input points
per common
ON voltage/ON current
OFF voltage/OFF current
Input impedance
Response
time
Operating mode indicator
Rated voltage
Operating voltage range
Allowed momentary power off time
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise resistance
Operating condition
Current consumption
Protection
Mass
General specifications
DC input specifications (X0 to X7)
X0 through X5 are inputs for the high-speed counter and have a fast response
time. If used as normal inputs, you should insert a timer in the program as
chattering and noise may be interpreted as an input signal.
Also, the above specifications apply when the rated input voltage is 24V DC
and the temperature is 25°C.
Item
OFF to ON
ON to OFF
Item
8 points (6 points for thermocouple input type)
Optical coupler
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA
8 points/common (6 points/common for
thermocouple input type)
Either the positive or negative of the input power
supply can be connected to common terminal.
19.2 V or less/4 mA or less
2.4 V or more/1 mA or more
Approx. 5.1 k (X0, X1)
Approx. 5.6 k (X2 to X7)
50 µs or less (X0, X1)
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
50 µs or less (X0, X1)
100 µs or less (X2 to X5)
2 ms or less (X6, X7)
LCD display (I/O monitor mode)
24 V DC
21.6 to 26.4 V DC
10 ms
0 to +55°C
–20 to +70°C
30 to 85%RH (non-condensing)
30 to 85%RH (non-condensing)
Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y4)
Output terminal (Y5)
Input terminals (COM, X0 to Xn)
Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y5)
Input terminals (COM, X0 to Xn)
10 to 55 Hz, 1 cycle/min.
Double amplitude: 0.75 mm, 10 min. on X, Y, and Z axes
98 m/s
1000V (p-p) with pulse widths 50 ns and 1 µs (based on in-house measurements)
Free from corrosive gases and excessive dust
200 mA or less (24 V DC)
IP66-compliant front section (Only when a rubber packing is used.)
Approx. 130 g
2
Description
or more, 4 times on X, Y, and Z axes
Note 1)
Note 1)
Note 1)
Note 1)
01/2004
∗1)
∗2)
∗3)
Number of input
Temperature sensor type
Input range
Accuracy
Resolution
Conversion time
Insulation method
Detection function of
wire disconnection
Temperature can be measured up to 330°C (626°F). When the measured temperature
exceeds 330°C (626°F) or the thermocouple wiring is disconnected, “K20000” is written
to the register.
Temperature conversion for thermocouple input is performed every 250 ms. The
conversion data is updated on the internal data register after the scan is completed.
The internal circuit and thermocouple input circuit are not insulated. Therefore, use the
nongrounding type thermocouples and sheath tubes.
Thermocouple input specifications
Power supply terminal, Function earth
Input terminal (A0, A1)
COM. (RS232C) terminal
Power supply terminal, Function earth
Input terminal (COM, X0 to Xn, A0, A1)
COM. (RS232C) terminal
Output terminals (Y0 to Y4)
Power supply terminal, Function earth
Input terminal (A0, A1)
COM. (RS232C) terminal
Output terminals (Y0 to Y5)
Description
Item
2 points (CH0: WX1, CH1: WX2)
Thermocouple type K
–30.0 to 300.0°C
±0.5%FS±1.5°C (FS = –30 to 300°C)
0.1°C
250 ms/2CH
Between internal circuit and thermocouple input
circuit: noninsulated
Between CH0 and CH1 of thermocouple input:
PhotoMOS insulation
Available
∗2)
∗1)
Description
(–22 to
∗3)
500 V AC for 1 minute
1500 V AC for 1 minute
500 V AC for 1 minute
Min. 100 M
(measured with 500 V DC)
572°F)