C25BNB240A Eaton / Control Automation, C25BNB240A Datasheet - Page 2

no-image

C25BNB240A

Manufacturer Part Number
C25BNB240A
Description
CONTACTOR; DP; 2 POLE; 40A; 120VAC COIL
Manufacturer
Eaton / Control Automation
Datasheet

Specifications of C25BNB240A

Coil Voltage
120
Current, Rating, Inductive
40
Current, Rating, Resistive
50
Horsepower, Motor, Max At 115 V
3
Horsepower, Motor, Max At 230 V
7.5
Number Of Poles
Double-Pole
Temperature, Operating, Maximum
+70 °C
Temperature, Operating, Minimum
–25 °C
Insulation Voltage
690 V
Contacts
Double Break
Magnet Coil
Class F, 155°C
Operating Temperature Range
–13 to 158°F (–25 to +70°C)
Terminal Wire Range — Hex Washer Head Screws
16-10 AWG, 30 Lb.-In. Torque Rating
Mounting Position
Vertical, Horizontal or Tabletop
2
Contents
Description
Compact 1- and 2-Pole
Product Description
Cutler-Hammer
double-pole, Type C25 contactors from
Eaton’s electrical business feature a
compact, efficient design with a low
VA coil and straight-through wiring.
New contactor housing design effec-
tively limits dust and other contami-
nants from magnet structure —
reduces or eliminates noise. These
economically priced, UL recognized/
CSA certified, ampere rated devices
are well suited for use in heating/air
conditioning, refrigeration, data pro-
cessing and food service applications.
Contactors 20 – 40A
Product Description . . . . . . . 2
Standards and
Technical Data —
Options . . . . . . . . . . . . . . . . . 2
Dimensions . . . . . . . . . . . . . 3
Product Selection . . . . . . . . 3
Definite Purpose Control
Contactors
20 – 40A, Compact 1- and 2-Pole — C25
Certifications . . . . . . . . . . . 2
Specifications . . . . . . . . . . 2
Compact 2-Pole
®
20 – 40A, single- and
Page
Standards and Certifications
Technical Data — Specifications
For more information visit: www.eaton.com
UL Recognized Components: UL File
Number E1491, Guides NLDX2 and
NLDX8
CSA Certified Components: CSA
C22.2 No. 14-05, File Number
238083 Class 3211 84
IEC 60947-4-1
EN 60947-4-1
Insulation Voltage: 690V
Current Rated and hp/kW Rated
Contacts: Double Break
Magnet Coil: Class F, 155°C
Contact Arc Covers are standard on
all Contactors
Standard Power Terminals —
Contactors are marked with Line
and Load Terminal Designations
Operating Temperature Range:
-13 to 158°F (-25 to 70°C)
Terminal Wire Range —
Mounting Position: Vertical,
Horizontal or Tabletop
5/16" Hex Washer Head Screws
Quad (4) Quick Connect Terminals
on all Line and Load Terminals
Box Lugs available as option
Hex Washer Head Screws:
16 – 10 AWG, 30 lb-in torque
rating
Box Lugs: 16 – 10 AWG, 35 lb-in
torque rating; 8 AWG, 40 lb-in
torque rating; 6 – 4 AWG, 45 lb-in
torque rating
Table 2. Coil Characteristics
One-Pole
Two-Pole
Options
Table 3. Compact Options —
Factory Installed
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . 1CD-5C
AC Coil
Voltage
50/60 Hz
120
208/240
277
120
208/240
277
480
Description
Box lugs with quick connects for
20 – 40A contactors:
To order replace letter in the 6th posi-
tion of Catalog Number with letter F.
EXAMPLE: C25BNF240A
24
24
ARI 780/790 Standard
RoHS Compliance
1-Pole
1-Pole with shunt
2-Pole
Max.
Inrush
VA
33
33
33
33
41
41
41
41
41
* Consult Sales Office for Pricing
Max.
Sealed
VA
6
6
6
6
6.5
6.5
6.5
6.5
6.5
PG03502001E
Max.
Sealed
Watts
2
2
2
2
3
3
3
3
3