FP-PS24-050E Panasonic Electric Works, FP-PS24-050E Datasheet - Page 10

no-image

FP-PS24-050E

Manufacturer Part Number
FP-PS24-050E
Description
POWER SUPPLY, 24VDC POWER SUPPLY, 2.1A
Manufacturer
Panasonic Electric Works
Datasheet
FP0 PROFIBUS DP Slave or Remote I/O Unit
For cost effective control of distributed field device
The FP0 DPS2 can operate either as a DP slave module or as a remote I/O
system to which different decentralised inputs and outputs can be
connected. A DIP switch can be used to switch between the two modes:
Mode 1:
DP-Slave module. Connect the FP0 or FP (Sigma) CPU + expansion
modules to the PROFIBUS network.
Mode 2:
Remote I/O. Connect up to three expansion modules without CPU to the
PROFIBUS network.
In Remote I/O mode the unit can be connected to any PLC which offers a
PROFIBUS communication interface, making it totally independent of
NAiS PLCs.
10
Item
Type designation
PROFIBUS standards complied with
Baud rates
Range of adresses that can be set
PROFIBUS connection
Configuration
FP0 communication
Power supply
Max. power consumption
FP0-DPS Specifications
up to 96 transistor I/O or up to
Configuration with digital I/O
48 relay I/O are possible
DP Slave Remote I/O
FP0 DP Slave
Remote I/O
DP-Slave
FP2 DP or FMS Master
with analogue I/O up to 12 outputs or
DP Slave Remote I/O Configuration
thermocouple inputs are possible
FP0 DP Slave unit, Ord. No. FP0DPS2
EN 50170, DIN 19245 Part 1 and Part 3
9.6 / 19.2 / 93.75 / 187.5 / 500 / 1,500 / 3,000 / 6,000 / 12,000 Kbaud
automatic baud rate detection
0..125
9-pin D-sub connector
2 words input / 2 words output, up to 6 words input / 6 words output if no other expansion is connected
Remote I/O, max. 3 FP0 expansion units
Via FP0 system bus
24VDC (21.6VDC … 26.4VDC)
100mA
24 analogue inputs or up to 24
FP (Sigma) DP Slave
10/2004
Remote I/O
(Master)
(Slave)
(Slave)
PLC
PLC
Description
Special developed software tools ensure
easy configuration and start-up of
PROFIBUS products.
AFP86910

Related parts for FP-PS24-050E