WMZT3C15 Eaton / Control Automation, WMZT3C15 Datasheet

no-image

WMZT3C15

Manufacturer Part Number
WMZT3C15
Description
CIRCUIT BREAKER, TYPE WMZT, 10KA, 3 POLE, 15A, C CURVE
Manufacturer
Eaton / Control Automation
Type
Thermal/Magneticr
Datasheet

Specifications of WMZT3C15

Actuator Type
Toggle
Brand/series
WMZT
Characteristic
C
Current, Rating
15 A
Dimensions
105 × 17.7 (per pole) mm
Mounting Type
DIN Rail
Number Of Poles
3
Special Features
Trip Indicator
Termination
Screw
Voltage, Rating
48/240 VDC/VAC
Lead Free Status / Rohs Status
RoHS Compliant part
UL 489 DIN Rail
Miniature Circuit Breakers
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers
2
4
6
1

Related parts for WMZT3C15

WMZT3C15 Summary of contents

Page 1

... UL 489 DIN Rail Miniature Circuit Breakers Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers ...

Page 2

... Relays • UPS • Power conditioners • 2 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers Features Complete range of UL 489 listed DIN rail mounted miniature • circuit breakers ampere current rating Complete family rated for 10 kAIC @ 277/480 Vac • Current limiting design provides fast short circuit interruption • ...

Page 3

... Products meet the requirements of the Canadian Electrical Code (CEC). Tripping characteristics Eaton WMZT branch circuit breakers are available with “C” and “D” tripping characteristics. C-curve devices are suitable for application where medium levels of inrush current are expected. Applications include small trans- formers, lighting, pilot devices, control circuits, and coils ...

Page 4

... Interrupting capacity UL/CSA IEC 60947 • Current limiting device • 3-Pole Catalog Number WMZT3CX0 WMZT3C01 WMZT3CX1 WMZT3C02 WMZT3C03 WMZT3C04 WMZT3C05 WMZT3C06 WMZT3C07 WMZT3C08 WMZT3C10 WMZT3C13 WMZT3C15 WMZT3C16 WMZT3C20 WMZT3C25 WMZT3C30 WMZT3C32 WMZT3C40 WMZT3DX0 WMZT3D01 WMZT3DX1 WMZT3D02 WMZT3D03 WMZT3D04 WMZT3D05 WMZT3D06 WMZT3D07 WMZT3D08 WMZT3D10 ...

Page 5

... Current limiting device • 3-Pole Catalog Number Current Rating) n WMZT3CX0T WMZT3C01T WMZT3CX1T WMZT3C02T WMZT3C03T WMZT3C04T WMZT3C05T WMZT3C06T WMZT3C07T WMZT3C08T WMZT3C10T WMZT3C13T WMZT3C15T WMZT3C16T WMZT3C20T WMZT3C25T WMZT3C30T WMZT3C32T WMZT3C40T Current Rating) n WMZT3DX0T WMZT3D01T WMZT3DX1T WMZT3D02T WMZT3D03T WMZT3D04T WMZT3D05T WMZT3D06T WMZT3D07T WMZT3D08T ...

Page 6

... Bus Bar Shroud Extension Terminal — – 14 AWG) Bus Connector — Conductors Contact sales office for availability. 6 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers Tripping Signal Switch WMZSAUXTRIP, WMZTAUX Design according to IEC/EN 60947-5-1, IEC/EN 62019 Catalog Number • Field installable WMZSAUXTRIP • ...

Page 7

... Onto Switching Dev. IP40 Finger and Hand Touch Safe According to BGV A3, ÖVE-EN 6 Lift Terminals 20 – 14 AWG M3 (Pozidrive Z0) 7 lb-in EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers WMZT Circuit Breakers ACCESSORIES WMZTAUX 1NO + 1NC 250V 50/ 250 Vac 2A / 250 Vac ...

Page 8

... Finger and Hand Touch Safe According to BGV A3, ÖVE-EN 6 Terminals Open Mouthed / Lift Terminal Capacity 1 and 18 – 10 AWG 2 Wires 8 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers Bus Bar Block UL489 (Pin) Tested according to UL 489 • Do not cut • Extension terminal 35 mm • ...

Page 9

... AWG UL 486B # 8 – 12 AWG UL 486E # 6 – 1 AWG UL 489 DIN Rail Miniature Circuit Breakers Lockout Attachment WMZPLK IEC/EN60947-2 2.5 – Tightening Torque of Terminal Screws ≥ 2.3 Nm ≥ 2 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers WMZT Circuit Breakers ACCESSORIES WMZT3PSHROUD WMZT35EXT 9 ...

Page 10

... Terminal Fastening Torque AWG 18-21: 21 lb-in AWG 10-8: 25 lb-in AWG 6: 36 lb-in Mounting Independent of Position Calibration temperature UL 489, CSA C22.2 No.5 40°C IEC 60947-2 30°C 10 EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers Dimensions (mm) 3-pole 17.7 Power loss Characteristic [A] P [W] 0.5 1 ...

Page 11

... Let-Through Energy Characteristic C (0.5 – 20A), 277V Characteristic D (0.5 – 20A), 277V UL 489 DIN Rail Miniature Circuit Breakers Characteristic C (25 – 40A), 240V Characteristic D (25 – 40A), 240V EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers WMZT Circuit Breakers TECHNICAL DATA 11 ...

Page 12

... Influence of Ambient Temperature T on Load Carrying Capacity Ambient Temperature T [°C] Maximunm Load I at ambient temperature EATON CORPORATION UL 489 DIN Rail Miniature Circuit Breakers 25°C 30°C 0.5 0.5 0.5 1.1 1.1 1.0 1.6 1.6 1.6 2.2 2 ...

Related keywords