60143 TELEMECANIQUE, 60143 Datasheet - Page 5

no-image

60143

Manufacturer Part Number
60143
Description
Circuit Breaker; Mag; Hndl; Cur-Rtg 8A; DIN Rail; 2 Pole; Vol-Rtg 240/125VAC/VDC; C
Manufacturer
TELEMECANIQUE
Type
Magneticr
Datasheet

Specifications of 60143

Actuator Type
Handle
Brand/series
Multi 9™
Characteristic
C
Current, Rating
8 A
Dimensions
1.42"Wx4.21"Hx3"D
Mounting Type
DIN Rail
Number Of Poles
2
Standards
UL 489
Termination
Box Lug
Voltage, Rating
240/125 VAC/VDC
Small Size — L × W × H, Mm
107 × 18 (Per Pole) × 75
Two Trip Curves
C — 7-10 Times Rating; D — 10-14 Times Rating
Ampere Ratings
From 0.5 to 35 Amps
Dc Ratings (c-curve Only)
1-Pole — 60 VDC; 2-Pole — 125 VDC
03/2008
UL 489 Listed 240 Vac C60 Circuit Breakers (AC)
A selected range of Multi-9 circuit breakers rated 240 V are UL 489 Listed. Unlike UL 1077
Supplementary Protectors, these UL 489 circuit breakers can be used for branch circuit protection as
required by the National Electrical Code.
As shown in tables Table 5 and Table 6, the UL 489 Listed products are available in C and D curves.
They include devices ranging from 0.5 to 35 A.
UL 489 Listed Multi 9 C60 Circuit Breakers
Table 4:
Standard Features
High Voltage Withstand
Connector: Box Lug
Connector: Ring Tongue
Mounting
Degree of Protection
Temperatures
Plug-On Auxiliary Modules with
Mechanical Linkage:
Tropicalization
Number of Operating Cycles
See specifications Table 2 for dimensions, weights and interrupting ratings
Fast closing: Allows increased withstand to the high inrush currents of some loads.
Trip-free mechanism: Contacts cannot be held in the I-ON position when the C60 circuit breaker is
tripped automatically.
Positive indication of contact disconnect. Green mechanical indication on front face of circuit
breaker shows that all poles are open.
C curve: Overcurrent protection for all application types. Magnetic release operates from 7 to 10
times ampere rating (7 to 14 for DC applications).
1P
Specifications for UL 489 240 V Listed C60N Circuit Breakers
Rating
Connection
Use Single UL Listed or CSA Certified
Insulated Ring Tongue Only
Max Ring Terminal Width
35 mm DIN rail
Case
Terminals
Calibration
Storage
Operating
MN Undervoltage Trip
MX + OF Shunt Trip/Auxiliary Switch
OF Auxiliary Switch
SD Alarm Switch
Treatment 2
Electrical (O-C)
6 kV
Section 2—UL and CSA Rated Protection Devices
© 2002–2008 Schneider Electric All Rights Reserved
2P
UL 486A File No. E216919 (Use with Copper Wire Only)
0.5–25 A: 14–4 AWG (2–25 mm
Torque to 22 lb-in. (2.48 N•m)
30–35 A: 14–2 AWG (1–35 mm
Torque to 31 lb-in. (3.52 N•m)
Screw dia. 0.2 in. (5 mm)
Torque to 18 lb-in. (2.03 N•m)
IP40 as per IEC 529
IP20
25°C (77°F)
-40 to 80°C (-40 to 176°F)
-30 to 70°C (-22 to 158°F)
0.54 in. (14 mm)
Relative Humidity: 95% at 131°F (55°C)
6,000 load, 4,000 no-load
Multi 9
System Catalog
2
2
) Cables
) Cables
3P
15