57601405 Eaton / Control Automation, 57601405 Datasheet - Page 2

no-image

57601405

Manufacturer Part Number
57601405
Description
TOTALIZER; RATE METER/TACHOMETER; AMBASSADOR 4 PRESET COUNT CONTROL 115 VAC
Manufacturer
Eaton / Control Automation
Type
Totalizerr
Datasheet

Specifications of 57601405

Accuracy
±0.015% %
Connection Type
Screw
Cut Out, Panel
2.677×2.677 "
Dimensions
2.946"L×5.6"W×2.946"H
Display Type
LCD
Function
Totalizer
Number Of Digits
8
Output Type
2 Relay + 2 Trn
Voltage, Input
115 VAC
Voltage, Supply
115 VAC
Protection
NEMA 4X Rating When Mounted with Gasket Provided Specifications
Rate Indicator — 1/tau; 6-digit; Presets
2
Outputs
Transistor — NPN Open Collector, Relay Outputs — SPDT
Lead Free Status / Rohs Status
RoHS Compliant part
Features
Standards and Certifications
Technical Data and
Specifications
Power Input
DC Power Output
Environmental
PG05400001E
AC/DC powered, 2-line LCD display
8-digit totalizer
1/Tau ratemeter
Totalizer and ratemeter scaling
Four user-configurable control
inputs
Up to two output relays
Two solid-state outputs
RS-485 Serial communications
Feet/Inches control available
UL Listed
CE Marked
AC Operation —
DC Operation: 10 – 15V DC opt.,
300 mA maximum
12V DC (±25%), 100 mA maximum
(includes all line and load varia-
tions)
Operating Temperature: 32 to 131°F
(0 to 55°C)
Storage Temperature: -4 to 158°F
(-20 to 70°C)
Operating Humidity: 85% Relative,
non-condensing
NEMA 4 rating when mounted with
gasket provided
115V AC (±15%) std., 50 to 60 Hz,
7W
230V AC (±15%) opt., 50 to 60 Hz,
7W
Cat. No. 57601401
Main Counter
Batch Counter
Totalizer
Count Input Speeds
Count Inputs
Type: Bi-directional
Digits: 6
Presets: Varies by Model
Reset modes: Auto or manual reset
to zero or preset
Scaler Range: 0.00001 to 9.99999
Decimal Point: 5 positions, (6 on 4-
preset models)
Output Latency: See Table 40
Type: Increment with main counter
recycle or final preset signal
Digits: 6
Presets: 1
Output Latency: < 1 mS
Type: Bi-directional, same or
opposite of main counter
Digits: 8
Scaler: Shared with main counter
Decimal Point: Tracks main counter
See Tables 42 and 43
Sink —
Source (high) —
Source (low) —
Counters, Panel Meters, Tachometers and Timers
Count Control
Ambassador Series — Durant
Impedance: 4.6k ohms to +5V DC
Voltage —
High: 3.5 to 34.0
Low: 0.0 to 1.9V DC
Impedance: 2.3k ohms to
common
Voltage —
High: 3.5 to 17.0V DC (100% duty
cycle)
Low: 0.0 to 1.9V DC
Impedance: 2.3k ohms to
common
DC Voltage —
High: 0.6 to 17.0V DC
Low: -17.0 to -0.6V DC
AC Voltage: 17V AC (48V Peak-
Peak) maximum
®
Control Inputs
Relay Outputs
Transistor Outputs (2)
Communication
Rate Indicator (Not available on models
57601-415 and 57601-485)
Connections
Impedance: 4.7k ohms to +5V DC
Voltage —
Type: SPDT contacts
UL Ratings: 250V AC, 360V A Pilot
Duty
Type: NPN open collector with tran-
sient protection
Maximum Voltage (OFF state):
30V DC
Maximum Current (ON state):
200 mA @ 1.3V DC
Type: RS-485
Format: 1 start bit, 7 data bits
(ASCII), 1 parity bit, 1 stop bit
Protocol: Opto-22 compatible
Speed: 300, 1200, 2400, 4800, 9600
and 19200 baud
Parity: Odd, Even, None (space
transmitted, ignore received)
Type:
Digits: 6
Presets: 2
Scaler Range: 0.00001 to 99999
Decimal Point: 5 positions,
programmable
Accuracy: ±0.015% of reading
Update Time: See Table 41
Zero Time: See Table 41
Type: Dual depluggable screw
terminal strips
Conductor Size: 14 – 22 AWG
(2.1 – 0.38 mm
stranded, or fused (preferred)
High: +3.7 to +24V DC
Low: 0.0 to 0.9V DC
Response: Minimum low 15 mS,
minimum high 15 mS
1/Tau
2
), 600V, solid,
43

Related parts for 57601405