56.OA12.1242C Altech Corp., 56.OA12.1242C Datasheet

no-image

56.OA12.1242C

Manufacturer Part Number
56.OA12.1242C
Description
Relay; E-Mech; Sfty; 4 NO, 2 NC; Cur-Rtg 8A; Ctrl-V 12DC; Vol-Rtg 400/250AC/DC; PCB Mnt
Manufacturer
Altech Corp.
Datasheet

Specifications of 56.OA12.1242C

Contact Form
4PST-NO, SPST-NC
Creeping Distance
> 8 mm (Contact⁄Coil)
Current, Rating
8 A
Function
Safety
Material, Contact
AgNi 10 + 0.2 um Au, AgCdO + 0.2 um Au, AgNi 10 + 5 um Au
Material, Cover
Thermoplast
Mounting Type
PCB
Number Of Pins
14
Power, Rating
2000⁄200 VA⁄W
Relay Type
Electro Mechanical
Resistance, Coil
180 Ohms
Standards
UL, CSA, TUV
Temperature, Ambient, Minimum
-25 °C
Temperature, Operating
-25 to +85 °C
Termination
Solder
Voltage, Breakdown
> 4 kV (Contact⁄Coil)
Voltage, Control
12 VDC
Voltage, Rating
400 VAC
Weight
38 g
Max. Switching Voltage
250 VDC, 400 VAC
Max. Switching Current
8 A
Relay Operate Time
20 mSec.
Relay Release Time
6 mSec.
Relay Contacts
4 NO/2 NC
Contact Material
AgCd O + 0.2 μmAu
Lead Free Status / Rohs Status
RoHS Compliant part
Relay operation voltage vs. ambient
temperature
U
U
18
n
n
n
n
n
n
n
n
n
n
n
N
B
Safety Relay
OA 5612
Features
n
n
n
n
n
n
n
n
n
n
n
n
n
n
1.4
1.2
1.0
0.8
0
6 output contacts
International approvals: TÜV, UL, cUL, CSA
Quality control check for each safety relay
Forced-guided contacts, all gold flash plated
Contact Gap > 0.5 mm throughout life of relay
Various contact materials,
mixed contact material optional
High coil voltage range
Very high switching voltage
High breakdown voltage: contact/coil > 4 KV
High creeping distance: contact/coil > 8 mm
Crown contacts
Solid connection between coil and contact housing
Compact size
Custom design available,
-coil voltage
-contact pressure
-operate/release time
-low power dissipation models
Nominal Coil Voltage.......................................................
Coil Power Dissipation..................................0.8 - 1.0 W
Max. Switching Voltage....................250V DC, 400V AC
Max. Switching Current.............................................8 A
Max. Switching Power—DC ..................................200W
Max. Switching Power—AC ...............................2000VA
Contact Switching Rate ........10 operations per second
Relay Operate Time...............................................20 ms
Relay Release Time.................................................6 ms
Operation Vibration.........................0.35 mm Ampl. max
Protection Rating ....................................................IP 40
.................................................6, 12, 24, 48, 60, 110, DC
.......................................................@ 10...200Hz, 3g max
20
40
Ambient Temperature
60
80
85
100°C
-IP67 washable
-coil resistance
Limitation factor for inductive loads
Operations =
Operations (ohmic) x limitation factor F
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.2
1
Power factor (cos ϕ )
Technical Data
0.4
0.6
Diagrams
0.8
1
n
n
n
n
n
n
n
n
Maximum switching power curve
Safe disconnection, no remaining arc,
max. 1 operation/sec.
250
200
150
100
50
0
Contact Arrangements....................................................
Contact Material ..............................................................
Mechanical Life.........................50x10
Electrical Life ...............AgSnO
Ambient Temperature ...................................-25...+85°C
Cover Material .............................................Thermoplast
Weight........................................................................38 g
More detailed data upon request
......................................2NO/4NC, 3NO/3NC, 4NO/2NC
..AgNi10+0.2µmAu, AgSnO
.......................operation cycles @ 230V AC, 5A, cos ϕ=1
.......................operation cycles @ 230V AC, 8A, cos ϕ=1
.......................................AgSnO
1
Switching current l [A]
2 3 4 5 6 7 8
GERMANY
C
USA/CANADA
US
2
+0.2µmAu, AgNi10+5µmAu
10
10
10
7
5
3
2
7
5
3
2
2
7
6
5
2
>3x10
>1.5x10
CANADA
Mechanical life
0.5
6
Switching capacity P [kVA]
5
operation cycles
, AgNi10 >2x10
1.0
5
, AgNi10 >10
1.5
2.0
5
5

Related parts for 56.OA12.1242C

56.OA12.1242C Summary of contents

Page 1

Safety Relay OA 5612 Features 6 output contacts n International approvals: TÜV, UL, cUL, CSA n Quality control check for each safety relay n Forced-guided contacts, all gold flash plated n Contact Gap > 0.5 mm throughout life of relay ...

Page 2

Safety Relay 5612 Data Relay Data Rated Voltage Voltage Range Resistance 6V 4.2 - 8.4V 12V 8.4 - 16.8V 24V 16.8 - 33.6V 48V 33.6 - 67.2V 60V 42.0 - 84.0V 12100 Ω 110V 77.0 - 145.0V Footprints (Note: Shown ...

Related keywords