XTSC012BBA Eaton / Control Automation, XTSC012BBA Datasheet - Page 2

no-image

XTSC012BBA

Manufacturer Part Number
XTSC012BBA
Description
MANUAL MOTOR CONTROLLER; 8-12A; FRAME B MMP W/FRAME B CONTACTOR 1NO; 120VAC COIL
Manufacturer
Eaton / Control Automation
Type
Motorr
Datasheet

Specifications of XTSC012BBA

Brand/series
XT Series
Coil Voltage
120
Current, Input
12 A
Current, Rating Max
12
Dimensions
45mmL×95.7mmW×209.2mmH
Frame Contactor
B/B
Horsepower, Max, 3 Phase, At 200 V
3
Horsepower, Max, 3 Phase, At 240 V
3
Horsepower, Max, 3 Phase, At 480 V
7.5
Horsepower, Max, 3 Phase, At 600 V
10
Ip Rating
IP20
Motor, Amp, Full Load
8-12
Mounting Type
DIN Rail
Power, Rating
5.5 kW
Primary Type
Motor Controller
Standards
CE
Voltage, Supply
120 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
For Use With
3-Phase Motor
May 2007
Standards and Certifications
UL 508 Type F Combination Motor
Controller
Note: For Type 2 Coordination of MMCs,
see Tables 247 through 249 on Pages 199
and 200.
Protection in Different Controller
Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL listed
Line Side Adapter (see Table 221). This
type of controller is a legitimate short
circuit protective device and discon-
nect means for the downstream motor.
It does require an upstream feeder
short circuit protective device, but
does not require a dedicated branch
circuit protection or a disconnect
means if used with a Line Side
Adapter. A UL 508 Type E rating means
that the unit clears a fault and does not
experience any welding of the power
poles. A UL 508 Type E self-protected
manual motor controller will remain
fully functional should a short circuit
within its ratings occur. E.g. XTPR.
An XT UL 508 Type F Self-protected
Combination Motor Controller consists
of a UL Listed Type E Self-protected
Manual Combination Starter/Motor
Controller, a UL Listed Contactor, and
a UL Listed Line Side Adapter (see
Table 221). While the UL 508 Type E
self-protected manual motor protector
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the downstream motor,
the contactor is not “self-protected.”
E.g. XTFC, XTFR.
In addition, as a complete assembly or
modular components, the device
should have Type 2 Coordination certi-
fication. Type 2 Coordination means
the Starter or the Controller must
exhibit little or no damage following a
major short circuit fault and should be
able to be returned to proper service
without replacing any parts.
CA03407001E
IEC Type 2 Approved per
IEC 60947-4-1
UL Listed File No. E245398
CE Mark
Table 221. MMC and CMC Applications
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
For more information visit: www.eaton.com
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMC = Manual Motor Controller
XTSC / XTSR
XT IEC Power Control
Combination Motor Controllers
Product Family Overview
Using the in-panel Main
SCPD
without a factory
assembled LSA.
Not required
Manual Motor Controller
Line Side Adapter (LSA)
Group Installation
XT IEC Manual & Combination Motor Controllers
and an MMC
Only Upstream Feeder SCPD
assembled LSA; no dedicated in-panel Main SCPD
for CMC.
UL 508 Type F Combination Motor Controller
XTFC / XTFR
Combination Motor Controller
Required — Factory
Assembled
Line Side Adapter (LSA)
required with factory
175