57701441 Eaton / Control Automation, 57701441 Datasheet - Page 3

no-image

57701441

Manufacturer Part Number
57701441
Description
DIGITAL PROCESS METER; ECLIPSE DPM; 85-265VAC; 5A AC; RELAY OUT
Manufacturer
Eaton / Control Automation
Type
Currentr
Datasheet

Specifications of 57701441

Cut Out, Panel
1/8 DIN
Digit Height
0.56
Dimensions
4.04"L×2.19"H×3.31"D
Display Digit Height
0.56 "
Display Type
LED
Function
Current/Process
Measuring Range
5 A
Number Of Digits
4
Output
2
Special Features
Scalable Display
Voltage, Supply
85 to 265 VAC
Protection
NEMA 4X when Mounted with Gasket Provided
Lead Free Status / Rohs Status
RoHS Compliant part
60
Environmental
RS-485 Serial Communication —
Operating Env.: Indoor use to 2000
meters
Temperature —
Humidity: 0 to 85% RH, non-
condensing
Vibration: 2.5 Gs, 30 to 200 Hz
Shock: 30 Gs, 11 mS half sinewave
EMC/EMI: Per EN 61326-1 Industrial
Front Panel: NEMA 4X when
mounted with gasket provided
Agency Approval:
Pollution Deg. 2: Overvoltage
Category II
Counters, Panel Meters, Tachometers and Timers
Digital Panel Meters
Eclipse Series — Durant
Baud Rate: 1200, 2400, 4800, 9600
or 19,200, programmable
Parity: Even, odd or no parity
Address Range: 00 to 99 decimal
Protocol: Opto 22
Isolation Dielectric Strength:
2300V AC to signal inputs, relays,
and AC power input; 500V AC to
analog outputs and DC power
inputs
Operating: 32 to 122°F (0 to 50°C)
Storage: -4 to 158°F (-20 to 70°C)
CE EMC immunity and emissions
requirements were met using
shielded wiring on the RS-485,
analog output and signal input
lines. The shields were connected
to earth ground at the Eclipse end
of the shields.
Conducted emissions
requirements were met assuming
that the AC signal input would not
be connected directly to the AC
Mains.
The measurement error during RF
immunity testing was less than
±5% of full scale. In addition,
models with an AC signal input
had measurement error of less
than +25% of full scale during RF
immunity testing of the RS-485 at
frequencies below 1 MHz.
®
compatible
®
Catalog Number Selection
Table 61. Eclipse Series Digital Panel Meters Numbering System
Output Options 0, 2, 4 are not available for models -41X and -43X.
0 = DC (9 – 30V DC)
1 = AC (85 – 265V AC)
0 = DC Volt
1 = AC Volt TRMS
2 = DC Amp
3 = AC Amp TRMS
4 = 5A AC TRMS
5 = Process (4 – 20 mA,
6 = Temperature (J, K, T,
Power Supply
0 – 10V, 1 – 5V)
PT100 RTD)
5 7 7 0 X - 4 X X
Input Option
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CC-1
0 = No Option
1 = Dual Relay
2 = Analog Output (4 – 20 mA
3 = Dual Relay, Analog Output
4 = RS-485 Communications
5 = Dual Relay, RS-485
6 = Analog, RS-485 (4 – 20 mA
7 = Dual Relay, Analog, RS-485
and 0 – 10V)
(4 – 20 mA and 0 – 10V)
and 0 – 10V)
(4 – 20 mA and 0 – 10V)
Output Option
PG05400001E