G79-O50C Omron, G79-O50C Datasheet - Page 13

no-image

G79-O50C

Manufacturer Part Number
G79-O50C
Description
50CM OUTPUT CABLE
Manufacturer
Omron
Datasheet

Specifications of G79-O50C

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
G79O50C
Note: Connecting Cable (CPM2C-CN111, CS1W-CN114, or CS1W-CN118) is required to connect to the communications peripheral /RS-232C
Communications Specifications
DeviceNet
Note: 1. A terminator must be connected to both ends of the trunk line.
98
Item
High-speed counter
functions
Quick-response inputs
Pulse output
Synchronized pulse control
Input time constant
(ON response time = OFF response time)
Clock
Communications functions
Power failure backup function
Memory backup
Self-diagnostic functions
Program check
Programming
devices
Communications protocol
Connection form
Baud rate
Communications media
Communications dis-
tance
Max. number of connecting nodes
Error control checks
port.
2. The maximum network length is the lenght of the trunk line.
3. When Thin Cable is used for the main line, the main line must be 100 m or less in length.
High-speed counters
Interrupt inputs
(counter mode)
Programming
Console
CX-One
Counter interrupts
Count-up
interrupts
Baud rate
Specification
1 interrupt (set value comparison or set-value range comparison)
2 interrupts (Used for both external interrupts inputs and quick-response inputs.)
2 interrupts (Used for both external interrupts inputs and quick-response inputs.)
Min. input pulse width: 50 s max.
10 Hz to 10 kHz each, and no direction control: 1 point with trapezoid acceleration/deceleration,
10 Hz and 10 kHz with no direction control: or 2 points with variable duty-ratio outputs
Can be set for CPU Unit inputs and Expansion Unit inputs only
(1, 2, 3, 5, 10, 20, 40, or 80 ms)
Equipped with clock (built-in RTC)
tions.
RS-232C port: Supports Host Link, no-protocol communications, 1-to-1 Link, or 1-to-1 NT Link connections.
Data in HR, AR, Counter (CNT), and Data Memory (DM) areas is held.
Memory backup (lithium battery: 2 years lifetime): DM area, HR area, AR area, and counter values
CPU error (watchdog timer), memory errors, communications errors, setting errors, battery errors, and expansion I/O
bus errors
C200H-PRO27, CQM1-PRO01, or CQM1H-PRO01
Windows 2000 / XP
1 counter (single phase at 20 kHz or 2 phases at 5 kHz)
2 points (Used for both external interrupts inputs and counter mode interrupt inputs.)
2 points with no acceleration/deceleration,
1 point
Peripheral port: Supports Host Link, peripheral bus, no-protocol communications, and Programming Console connec-
Non-volatile (flash) memory: Program, read-only DM area, and PC Setup
No END instruction, programming errors (checked when operation is started)
DeviceNet
Combination of multi-drop and T-branch connections (see note 1)
500, 250, or 125 kbps (switchable)
Special 5-conductor cable (2 signal lines, 2 power supply lines, and 1 shield line)
500 kbps:
Max. network length (see note 2):100 m max. (see note 3)
Main line length:6 m max.
Total branch line length:39 m max.
250 kbps:
Max. network length (see note 2):250 m max. (see note 3)
Main line length:6 m max.
Total branch line length:78 m max.
125 kbps:
Max. network length (see note 2):500 m max. (see note 3)
Main line length:6 m max.
Total branch line length:156 m max.
64 (63 slaves and 1 master)
CRC error, node address duplication check, and scan list verification