Specifications of ATV212HD18N4

Supply Voltage Range
380VAC To 480VAC
No. Of Phases
3
Power Rating
18kW
Rohs Compliant
Yes
Output Current
37A
Altivar 212 Drive
Typical air handling applications:
• HVAC supply and return fans
• Exhaust and ventilation fans
• Cooling tower fans
• Energy recovery wheels
6
Run command
Speed command
Run status
Speed feedback
Fault Output
Loss of Speed
Automatic Restart
Skip Frequency Bands
Local/Remote Control
Catch on the Fly
Damper Control Relay
Smoke Purge Override
Broken Belt Detection
PID Control
Sleep/Wake-up
Pump Jam Management
Motor direction protection
Integrated Fan and Pump Functionality
Input to drive by remote contact from the BAS, 24 vdc supplied by VFD
Input to drive from the BAS; typically 4-20mAdc or 0-10 Vdc
Output contact from drive to the BAS; 1 N.O. contact on drive
Analog output from drive to the BAS; typically 4-20mAdc, or assignable to meter values
Output contact from drive to the BAS; 1 N.O. & 1 N.C. contact on drive
Configuration to run at last speed or a pre-defined speed on loss of speed command
Selectable configuration to automatically restart after cause of fault is cleared
Three skip frequency settings with adjustable bandwidth to tune out resonating frequencies
in piping or ductwork
Keypad selectable: local keypad control for Run, Stop and speed control or from remote signal
from BAS
Configuration to initiate speed and direction search to provide smooth start of windmilling fans
Output on the drive to control damper opening sequence, and wait for feedback to start the motor
Logic Input on the drive configured to run the motor at configured speed for forced ventilation
Configuration to detect under load condition and initiate alarm sequence
Set point and feedback inputs for proportional, integral, and derivative control
Configuration in the drive to stop the pump at low or no flow and re-start on demand for flow
Configuration to manage blocked pump impeller
Configuration to prevent operation in reverse direction
Typical pumping applications:
• Cooling tower pumps
• Chilled water and hot water pumps
• Fountain pumps
• Domestic water supply pumps