(110127)
HR2S
Safety Relay Modules
Compact Design and Maintenance Improvements
for Outstanding Usability!
Compact Design and Maintenance Improvements
for Outstanding Usability!
Performance level (PL)
Compliant with
EN ISO 13849-1
Category 4
HR2S-301P
e
European and North American (NRTL)
TÜV SÜD
HR2S-301N
SIMPLE
HR2S-332N-
T075/T15/T30
With time-delay output
COMPACT
SAFETY

Related parts for HR2S-332N-T15

HR2S-332N-T15 Summary of contents

Page 1

... Compact Design and Maintenance Improvements Compact Design and Maintenance Improvements for Outstanding Usability! for Outstanding Usability! HR2S-301P Compliant with e Performance level (PL) Category 4 EN ISO 13849-1 (110127) HR2S-301N SIMPLE TÜV SÜD European and North American (NRTL) HR2S-332N- T075/T15/T30 With time-delay output SAFETY COMPACT ...

Page 2

... Compact design enables installation in a narrow space HR2S-301P HR2S-332NT HR2S-301N HR2S-332NT- 075/15/30 Time-delay output 3NO (safety output) and 3NO (time-delay safety output) Time-delay output compliant with category 4 Time setting can be selected from 31 different time ranges · HR2S-332N-T075=0.5/1/1.5/2/2.5/3/3.5/4/4.5/5/5.5/6/6.5/7/7.5s · HR2S-332N-T15=1/2/3/4/5/6/7/8/9/10/11/12/13/14/15s · HR2S-332N-T30=2/4/6/8/10/12/14/16/18/20/22/24/26/28/30s (110127) ...

Page 3

... Weight (approx.) Note 1: UL and CSA are approved by TÜV SÜD America Inc., an accredited 2,500V AC, 1 minute NRTL. Note 2: HR2S-301N is recommended for use in category 4 safety 2,500V AC, 1 minute applications. The requirements of the safety category must be determined according to the safety equipment. We recommend that 2,500V AC ,1 minute you consult a third party organization ...

Page 4

... CN3 13–14 CN4 2 23–24 33–34 4 Note: 5.0A max. Category 3 or lower HR2S-301P 3.6A max. Category 4 Safety category is achieved by the entire control system. Take the connected safety equipment and wiring into consideration. Turn on DIP switch #3 on the receiver. (Yellow) EDM N ...

Page 5

... External start condition Protective fuse for the output of safety relay module S1: Emergency stop switch with 2NC contacts, safety switch (recommended) S2: Start Switch S33-S34: Feedback loop (110127) HR2S-301P/HR2S-301N Safety Relay Modules MANU mode Detecting Removing Object Object OSSD1 (ESPE) OSSD2 ( ESPE ) Start Switch ...

Page 6

... HR2S-301P/HR2S-301N Safety Relay Modules Safety Category 3 Circuit Example (using multiple emergency stop switches and a safety switch) Door Cover HS5E-DD4401-G Interlock Switch with Solenoid 24V HS9Z-A51 21 Actuator XW1E-BV402 Emergency 22 Stop Switches A1 S11 S21 S22 HR2S-301N Operation Chart Using an emergency stop switch AUTO mode ...

Page 7

... All dimensions in mm Terminal position (76.7) Terminal position (95.7) 111 Package Quantity: 1 Part No. HR2S-332N-T075 HR2S-332N-T15 HR2S-332N-T30 250V AC / 30V DC (resistive load) (Note 7) Category 3 or lower: 5.0A maximum Category 4 or lower: 3.6A maximum AC15 240V cosø=0.3 DC13 ...

Page 8

... HR2S-332N-T075/T15/T30 Safety Relay Modules Terminal Arrangement Part Description 5 3 Part No S33 SAFETY ERR RELAY MODULE 1 0.5 HR2S-332N-T075 max. 7.5sec POW 0.5 4 MANU max. 7.5sec RESET 13 6 AUTO RESET S11 S12 S21 S22 HR2S-332N-T075/T15/T30 Wiring Diagram Safety Category 4 Circuit Example (using an emergency stop switch) ...

Page 9

... HR2S-332N-T075/T15/T30 Safety Relay Modules Safety Category 3 Circuit (using multiple emergency stop switches) Door Cover HS5E-DD4401-G Interlock Switch with Solenoid 24V HS9Z-A51 S2 21 Actuator XW1E-BV402 Emergency 22 Stop Switches A1 S11 S21 S22 ESC: External Start Condition F1 to F4: Fuse 3. Safety Contactor S1: HS5E-DD4401-G Interlock Switch with Solenoid ...

Page 10

... HR9Z-PE1 Residual Risk (EN ISO/ISO12100-1) The wiring diagrams in this catalog have been tested under actual operating conditions. The HR2S safety relay module can be used in a safety circuit by connecting to the safety equipment compliant to applicable standards. Consider residual risk in the following circumstances. a) When circuits other than described in this catalog are used ...

Page 11

... Except when connecting safety light curtains. Precautions when using multiple HR2S modules A single switch (see SW1 in the diagram below) cannot be connected to multiple inputs. Use switches with independent contacts. (Do not connect one safety device to two HR2S safety inputs in a parallel connection.) SW1 SW1 S11 ...

Page 12

... EN954-1 control category 4 compliant. Specifications and other descriptions in this catalog are subject to change without notice. IDEC CORPORATION (USA) 1175 Elko Drive, Sunnyvale, CA 94089-2209, USA Tel: +1-408-747-0550 / (800) 262-IDEC (4332) Fax: +1-408-744-9055 / (800) 635-6246 E-mail: opencontact@idec.com IDEC CANADA LIMITED 3155 Pepper Mill Court, Unit 4, Mississauga, ...