B25673A4072A540 EPCOS Inc, B25673A4072A540 Datasheet - Page 6

Film Capacitors - Additional Technologies MKK440-D-7.5-02

B25673A4072A540

Manufacturer Part Number
B25673A4072A540
Description
Film Capacitors - Additional Technologies MKK440-D-7.5-02
Manufacturer
EPCOS Inc
Datasheet

Specifications of B25673A4072A540

Capacitance
41.1 uF x 3
Tolerance
- 5 %, + 10 %
Voltage Rating
440 Volts
Termination Style
Quick Connect
Dimensions
85 mm Dia. x 162 mm L
Product
PhaseCap Compact Capacitors
Lead Free Status / Rohs Status
 Details
Overpressure Disconnector
To ensure full functionality of an overpressure disconnector, the following must be observed:
1. The elastic elements must not be hindered, i.e.
2. The maximum allowed fault current of 10000 A in accordance with UL 810 standard must be
assured by the application.
3. Stress parameters of the capacitor must be within the IEC60831 specification.
Overcurrent and short circuit protection
Resonance cases
Resonance cases must be avoided by appropriate application design in any case. Maximum total
RMS capacitor current (incl. fundamental harmonic current) specified in technical data must not be
exceeded.
Re-switching vs. phase-opposition
In case of voltage interruption, a sufficient discharge time has to be ensured to avoid phase-
opposition and resulting high inrush currents
Vibration resistance
The resistance to vibration of capacitors corresponds to IEC 68, part 2–6.
Max. test conditions:
Test duration
Frequency range 1
Displacement amplitude
*corresponding to max. 98.1 m/s or 10 g
FK PC PM PFC
Please read Cautions and warnings and
Important notes at the end of this document.
Film capacitors – Power Factor Correction
PhaseCap Compact capacitors
Use HRC fuses or MCCBs for short circuit protection. Short circuit protection and connecting
cables should be selected so that 1.5 times the rated capacitor current can be permanently
handled.
HRC fuses do not protect a capacitor against overload – they are only for short circuit protection.
The HRC fuse rating should be 1.6 to 1.8 times rated capacitor current.
Do not use HRC fuses to switch capacitors (risk of arcing).
Use thermal magnetic over current relays for overload protection.
Connecting lines must be flexible leads (cables).
There must be sufficient space (min. 12 mm) for expansion above the connections. This will
enable a longitudinal extension of the can to secure the overpressure disconnector work.
Folding beads must not be retained by clamps.
6 h*
10 ... 55 Hz*
0.75 mm*
.