160NHG02BI-400 Cooper Bussmann, Inc., 160NHG02BI-400 Datasheet - Page 4

no-image

160NHG02BI-400

Manufacturer Part Number
160NHG02BI-400
Description
Nh Din Dual Indication Fuse Links Class Gg/gl, 400vac, 2 To 630 Amps, Sizes 000 To 3
Manufacturer
Cooper Bussmann, Inc.
Datasheet
Size 01 & 1 Technical Data
Dimensions - mm
23-04-09
NH DIN Dual Indication Fuse Links
Class gG/gL, 400Vac, 35 to 250 Amps, Sizes 01 & 1
Size 01
* I 1 is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements.
Metal Gripping Lugs
Part Numbers with
100NHG01B-400
125NHG01B-400
160NHG01B-400
35NHG01B-400
40NHG01B-400
50NHG01B-400
63NHG01B-400
80NHG01B-400
200NHG1B-400
224NHG1B-400
250NHG1B-400
SB-SB09367
Part Numbers with
100NHG01BI-400
125NHG01BI-400
160NHG01BI-400
35NHG01BI-400
40NHG01BI-400
50NHG01BI-400
63NHG01BI-400
80NHG01BI-400
200NHG1BI-400
224NHG1BI-400
250NHG1BI-400
Insulated Metal
Gripping Lugs
Size 01 & 1 Time-Current Characteristics
Size 1
Amp Rating
Form No.NH400V
100
125
160
200
224
250
35
40
50
63
80
Pre-arcing
Minimum
125000
180000
16000
24000
53000
80000
2400
3300
4200
6600
9600
I 2 t (Amps 2 Seconds)
Page 4 of 7
(Amps)
*I 1 120kA
@ 400Vac
111300
296000
462500
666000
10600
10400
16300
33600
56000
86400
7600
Watts
10.0
13.0
13.0
14.0
Loss
4.4
5.0
4.4
5.6
6.7
7.0
9.0
Data Sheet 720099
Net Weight
per Fuse
0.269kg
0.387kg
NH