125-JS6DT3 MTU Onsite Energy, 125-JS6DT3 Datasheet - Page 3

no-image

125-JS6DT3

Manufacturer Part Number
125-JS6DT3
Description
DIESEL ENGINE-GENERATOR SET
Manufacturer
MTU Onsite Energy
Datasheet
www.DataSheet4U.com
aPPlication Data
//
Manufacturer
Model
Type
Arrangement
Displacement: Cu In (lit)
Bore: in (cm)
Stroke: in (cm)
Compression Ratio
Rated RPM
Engine Governor
Max Power: Standby: bhp (kWm)
Regulation
Frequency
Air Cleaner
//
Total Oil System: gal (lit)
Engine Jacket Water Capacity: gal (lit)
System Coolant Capacity: gal (lit)
//
Electric Volts DC
Cold Cranking Amps Under 0°F (-17.8°C)
//
Fuel Supply Connection Size
Fuel Return Connection Size
Maximum Fuel Lift: ft (m)
Recommended Fuel
Total Fuel Flow: gal/hr (lit/hr)
Engine
Liquid Capacity (Lubrication)
Electrical
Fuel System
John Deere
6068HF285
4-Cycle
6-Inline
415 (6.8)
4.19 (10.6)
5 (12.7)
19:1
1,800
JDEC
237 (177)
±.25%
60 Hz
Dry
5.28 (20)
3.25 (12.3)
6 (22.7)
12
800
3/8” NPT
3/8” NPT
10 (3)
Diesel #2
28.3 (107.2)
3
/ / / /
125-JS6dt3
//
At 100% of Power Rating: gal/hr (lit/hr)
At 75% of Power Rating: gal/hr( lit/hr)
At 50% of Power Rating: gal/hr (lit/hr)
//
Ambient Capacity of Radiator: °F (°C)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H
Water Pump Capacity: gpm (lit/min)
Heat Rejection to Coolant: BTUM (kW)
Heat Rejection to Air to Air: BTUM (kW)
Heat Radiated to Ambient: BTUM (kW)
//
Aspirating: *SCFM (m
Air Flow Required for Rad.
Cooled Unit: *SCFM (m
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m
* Air density = 0.0739 lbm/ft
//
Gas Temp. (Stack): °F (°C)
Gas Volume at Stack
Temp: CFM (m
Maximum Allowable
Back Pressure: in. H
Fuel Consumption
Cooling - radiator System
Air requirements
Exhaust System
3
/min)
2
0 (kPa)
3
/min)
3
/min)
3
/min)
3
(1.184 kg/m
2
0 (kPa)
3
)
8.9 (33.7)
6.9 (26.1)
5 (18.9)
122 (50)
0.5 (0.12)
48 (180)
5,324 (93.5)
1,821 (32)
922 (16)
480 (13.6)
17,712 (502)
2,080 (59)
941 (505)
1,201 (34)
30 (7.5)

Related parts for 125-JS6DT3