AD960-30 COSEL CO., LTD., AD960-30 Datasheet - Page 3

no-image

AD960-30

Manufacturer Part Number
AD960-30
Description
Unit Type Power Module Dc-dc Convert
Manufacturer
COSEL CO., LTD.
Datasheet
AD
INPUT
OUTPUT
PROTECTION
CIRCUIT
ISOLATION
ENVIRONMENT
OTHERS
SPECIFICATIONS
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
Please refer to derating curve, because the rated load current depends
on cooling method that is convention cooling or forced air.
*1
*2
*
A-140
Measured by 20MHz oscilloscope or Ripple-Noise meter (equivalent to KEISOKU-GIKEN: RM101).
Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
When operated at pulse load, attach external capacitor at output line which is complying with the peak value of pulse current.
MODEL
VOLTAGE[V]
FREQUENCY[Hz]
EFFICIENCY[%]
INRUSH CURRENT[A]
LEAKAGE CURRENT[mA] 1.0max ( 60Hz , According to DEN-AN )
VOLTAGE[V]
CURRENT[A]
LINE REGULATION[mV]
LOAD REGULATION[mV] 300max
RIPPLE[mVp-p]
RIPPLE NOISE[mVp-p]
TEMPERATURE REGULATION[mV] 500max ( 0 to +45 C )
DRIFT[mV]
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 21.6 - 26.4
START-UP TIME[ms]
HOLD-UP TIME[ms]
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
REMOTE ON/OFF
INPUT-OUTPUT
INPUT-FG
OUTPUT-FG
OPERATING TEMP. , HUMID.AND ALTITUDE 0 to +65 C , 20 - 90%RH ( Non condensing ) ( Refer to DERATING CURVE ), 3 , 000m ( 10 , 000feet ) max
STORAGE TEMP. , HUMID.AND ALTITUDE -25 to +80 C , 10 - 95%RH ( Non condensing ), 9 , 000m ( 30 , 000feet ) max
VIBRATION
IMPACT
CASE SIZE/WEIGHT
COOLING METHOD
AD480
Unit type
ACIN 100V 30max ( Io=100% )
ACIN 200V 60max ( Io=100% )
Forced air 20 ( Peak 25 )
Convection 12 ( Peak 25 ) Ta=45 C
* 1
* 1
* 2
AD480-24
480
24V 20A
AD480-24
AC85 - 132 / 170 - 264 1 f ( User-selectable )
47 - 440
85typ
24
300max
240max ( 0 to +45 C )
480max ( 0 to +45 C )
100max
600max ( ACIN 100/200V , Io=100% )
15typ ( ACIN 100/200V , Io=100% )
Use terminal RC and G
AC1 , 500V 1minute , Cutoff current = 10mA , DC500V 100M W min ( At Room Temperature )
AC1 , 500V 1minute , Cutoff current = 10mA , DC500V 100M W min ( At Room Temperature )
AC500V 1minute , Cutoff current = 50mA , DC500V 100M W min ( At Room Temperature )
10 - 55Hz , 19.6m/s
196.1m/s
110 X 140 X 220mm ( W X H X D ) /3.0kg max
Forced air/Convection
2
( 20G ), 11ms , once each X , Y and Z axis
2
( 2G ), 3minutes period , 60minutes each along X , Y and Z axis
1
Ordering information
AD
2
480
AD480-30
300 ( Peak 720 )
30V 10 ( Peak 24 ) A Forced air
AD480-30
85typ
30
10 ( Peak 24 )
10 ( Peak 24 ) Ta=45 C
260max
420max
240max ( 0 to +50 C )
480max ( 0 to +50 C )
600max ( 0 to +50 C )
120max
28.5 - 33.0
3
-24
1Series name
2Output wattage
3Output voltage

Related parts for AD960-30