LTC1000-SF LEM, LTC1000-SF Datasheet - Page 2

no-image

LTC1000-SF

Manufacturer Part Number
LTC1000-SF
Description
Current Transducer
Manufacturer
LEM
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
LTC1000-SF
Quantity:
4
Dimensions LTC 1000-SF
Mechanical characteristics
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Front view
Top view
General tolerance
Fixing the transducer
Fastening torque max
Primary through-hole
Connection of secondary
Fastening torque max
± 1 mm
4 slots
4 screws M6
5 Nm
M5 threaded studs
2.2 Nm or 1.62 Lb.-Ft.
Faston 6.3 x 0.8 mm
(in mm. 1 mm = 0.0394 inch)
42 mm
6.5 mm
Remarks
I
Temperature of the primary conductor should not exceed
100°C.
Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
S
is positive when I
Secondary terminals
Terminal + : supply voltage + 15 .. 24 V
Terminal M : measure
Terminal - : supply voltage - 15 .. 24 V
Terminal E : shield
Connection
P
flows in the direction of the arrow.
Left view
or

Related parts for LTC1000-SF