kcd2-sr-1.lb Pepperl+Fuchs, kcd2-sr-1.lb Datasheet

no-image

kcd2-sr-1.lb

Manufacturer Part Number
kcd2-sr-1.lb
Description
Switch Amplifier
Manufacturer
Pepperl+Fuchs
Datasheet
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Features
• 1-channel signal conditioner
• 24 V DC supply (Power Rail)
• Dry contact or NAMUR inputs
• Relay contact output
• Fault relay contact output
• Line fault detection (LFD)
• Housing width 12.5 mm
• Up to SIL2 acc. to IEC 61508
Function
This signal conditioner transfers digital signals (NAMUR
sensors/mechanical contacts) from the field to the control
system.
The proximity sensor or switch controls a form A normally
open relay contact for the load. The normal output state is
reversed using switch S1. Switch S2 allows output II to be
switched between a signal output and an error message
output. Switch S3 enables or disables line fault detection of
the field circuit.
During an error condition, relays revert to their de-energized
state and LEDs indicate the fault according to NAMUR NE44.
A unique collective error messaging feature is available when
used with the Power Rail system.
Due to its compact housing design and low heat dissipation,
this device is useful for detecting positions, end stops, and
switching states in space-critical applications.
Connection
Switch Amplifier
400 Ω ≤ R ≤ 2 kΩ
10 kΩ
1+
2-
Front view
Switch 1 ... 4
Power Rail
Assembly
KCD2-SR-1.LB
ERR
24 V DC
Copyright Pepperl+Fuchs, Printed in Germany
KCD2-SR-
OUT/CHK
S1
S2
S3
S4
1
3
5
7
9 10
PWR
1.LB
I
2
4
6
8
II
5
6
7
8
10-
9+
II
I
24 V DC
2
Removable terminal
green
LED green:
Power supply
LED yellow/red:
Status output/
Fault signal
Place for labeling
Removable terminals
green
KCD2-SR-1.LB
1

Related parts for kcd2-sr-1.lb

kcd2-sr-1.lb Summary of contents

Page 1

... Switch 1 ... KCD2-SR-1. 10- ERR Power Rail Copyright Pepperl+Fuchs, Printed in Germany KCD2-SR-1.LB Removable terminal green LED green: Power supply LED yellow/red: Status output/ Fault signal Place for labeling Removable terminals green ...

Page 2

... Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. Subject to reasonable modifications due to technical advances. Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com switching cycles KCD2-SR-1.LB eff eff eff eff ...

Page 3

... Operating status Control circuit Initiator high impedance/ contact opened Initiator low impedance/ contact closed Lead breakage, lead short-circuit Factory settings: switch and 4 in position I Copyright Pepperl+Fuchs, Printed in Germany KCD2-SR-1.LB Position OFF II Input signal low input current ...

Related keywords