DS1200-3-004 EMERSON-NETWORKPOWER [Emerson Network Power], DS1200-3-004 Datasheet

no-image

DS1200-3-004

Manufacturer Part Number
DS1200-3-004
Description
1200 Watts Distributed Power System
Manufacturer
EMERSON-NETWORKPOWER [Emerson Network Power]
Datasheet
DS1200
1200 Watts
Distributed Power System
Distributed Power Bulk Front-End
Total Output Power: 1200 Watts
+3.3 Vdc Stand-by Output
Wide Range Input Voltage: 90 - 264 Vac
Special Features
• Active power factor correction
• EN61000-3-2 harmonic compliance
• Active AC inrush control
• 1U X 2U form factor
• 21.71 W / in
• +12 Vdc Output
• +3.3 Vdc stand-by
• No minimum load required
• Hot plug operation
• N + 1 redundant
• Internal OR’ing fets
• Active current sharing
• Built-in cooling fan
• I
• PMBus compliant
• EERPOM for FRU data
• Red/green bi-color LED status
• Internal fan speed control
• Fan Fail Tach Output Signal
• INTEL, SSI Std. logic timing
• INTEL, SSI Std. FRU data format
• Full digital control
• One year warranty
Safety
(5 V standby - consult factory)
(10 - 100% load)
(40 mm x 28 mm)
UL/cUL 60950 (UL Recognized)
NEMKO+ CB Report EN60950
EN60950
CE Mark
China CCC
2
C communication interface bus
3
Electrical Specifications
Input
Output
Input range:
Frequency:
Inrush current:
Efficiency:
Conducted EMI:
Radiated EMI:
Power factor:
Leakage current:
Hold up time:
Main DC voltage:
Stand-By:
Adjustment range:
Regulation:
Over current:
Over voltage:
Under voltage:
Turn-on delay:
Main output rise time:
180 - 264 (1200 W)
90 - 264 (1000 W)
47-63 Hz, single phase AC
40 Apk maximum inrush current
> 91% typical at high line 50% load
FCC Subpart J EN55022 Class B
FCC Subpart J EN55022 Class B
0.99 typical
1.40 mA @ 240 VAC
12 ms minimum
+12 V @ 100 A (high line)
+12 V @ 81.6 A (low line)
+3.3 Vsb @ 6 A (5 V @ 4 A available)
±5% on +12V only using I
+12 Vdc; +5% / -5%
+3.3 Vsb; +5% / -5%
+12 Vdc; latches off if overcurrent lasts over 1 second,
otherwise it is auto recovery (See Table 1 next page) +3.3 Vsb, 9 A
max (hiccup mode)
+12 Vdc; 13.2 - 14.4 Vdc
+3.3 Vsb; 3.76 - 4.30 Vdc
+12 Vdc; 9 - 10.8 V (latch off)
2 second max, 5 - 50 mS, monotonic rise
5 - 50 mS, monotonic rise
2
C
Embedded Power for
Business-Critical Continuity
Rev. 9.10.09_22
DS1200
1 of 4

Related parts for DS1200-3-004

DS1200-3-004 Summary of contents

Page 1

... Over current: +12 Vdc; latches off if overcurrent lasts over 1 second, otherwise it is auto recovery (See Table 1 next page) +3.3 Vsb max (hiccup mode) Over voltage: +12 Vdc; 13.2 - 14.4 Vdc +3.3 Vsb; 3.76 - 4.30 Vdc Under voltage: +12 Vdc 10.8 V (latch off) Turn-on delay: 2 second max mS, monotonic rise Main output rise time mS, monotonic rise Embedded Power for Business-Critical Continuity Rev. 9.10.09_22 2 C DS1200 ...

Page 2

... Set Point Model Number Voltage Set Point Tolerance DS1200-3 12.0 Vdc ±0.2% DS1200-3-002 12.0 Vdc ±0.2% DS1200-3-003 12.0 Vdc ±0.2% DS1200-3-004 12.0 Vdc ±0.2% *Over current latches off if overcurrent lasts over 1 seconds, otherwise it is auto recovery. 1400 1200 1000 800 600 400 200 0 0 -10° °C ; 50% power derating at 70 °C -40 ° ...

Page 3

... WAVE LENGTH: 565 AIRFLOW DIRECTION 279.4 ± 1.0 200.9 (3X) (200.9) LABEL MODEL 3.2 8.0 275.5 ± 0.7 200.9 EMI GASKET - LEIRD 77-018 Embedded Power for Business-Critical Continuity 7.02 ± 0.80 PROGRAMMING WINDOW 5.7 ± 0.5 18.4 ± 0.5 7.2 ± 0.5 68.8 6.0 (2X) 1.5 X 45° CHAMPER 9.0 RECOMMENDED KEY HEIGHT IS 2.5MM MAX. Rev. 9.10.09_22 DS1200  of 4 39.9 ± 0.5 15.3 ± 0.5 ...

Page 4

... Address BIT 1 Signal S_INT (Alarm) D4 STAND-BY RMT SENSE D5 STAND-BY D6 STAND-BY RETURN Embedded Power for Business-Critical Continuity Rev. 9.10.09_22 DS1200 Americas 5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698 Europe (UK) Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355 Asia (HK) ...

Related keywords