SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
OUTPUT NUMBER
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
AC OK
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
60W Single Output with Battery Charger(UPS Function)
Note.3
Note.2
PSC-60A
CH1
13.8V
2.8A
0 ~ 4.3A
59.34W
120mVp-p
CH1: 12 ~ 15V
800ms, 50ms/230VAC
50ms/230VAC
90 ~ 264VAC
47 ~ 63Hz
1.6A/115VAC
COLD START 30A/115VAC
<1mA / 240VAC
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
10.5 0.5V
TTL open collector output, ON : AC OK ; OFF : AC Fail ; Ice : max. 30mA@ 50VDC
TTL open collector output, ON : Battery Low ; OFF : Battery OK ; Ice : max. 30mA@ 50VDC
Battery low voltage < 11V
-20 ~ +70
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
589.7K hrs min.
101.6*50.8*29mm (L*W*H)
0.13Kg; 96pcs/13.5Kg/0.89CUFT
84%
1.0%
0.5%
0.5%
0.03%/
(0~50 ) on CH1 output
(Refer to output load derating curve)
I/P-FG:1.5KVAC
127 ~ 370VDC
1A/230VAC
MIL-HDBK-217F (25 )
10ms/115VAC at full load
1600ms, 50ms/115VAC at full load
CH2
13.8V
1.5A
--------
--------
--------
--------
--------
60A/230VAC
O/P-FG:0.5KVAC
PSC-60B
CH1
27.6V
1.4A
0 ~ 2.15A
59.34W
240mVp-p
CH1: 24 ~ 29V
84%
CH1:28.98 ~ 37.26V
21 1V
Battery low voltage < 22V
1.0%
0.5%
0.5%
P S C - 6 0
File Name:PSC-60-SPEC 2008-11-04