Backbox Mounting
The cabinet can be surface-mounted. The door is removable during installa-
tion by opening and lifting it off the hinges. The cabinet mounts using two
key slots at the top of the backbox and two additional 0.250" diameter holes
at the bottom.
Ordering Information
i³™ is a trademark and Gamewell® is a registered trademark of Honeywell International Inc.
F402
BB-17F
DP-FLEX
TR-1-R
52194
Northford, CT 06472-1610
A Honeywell Company
www.gamewell-fci.com
© 2006 Gamewell-FCI
Phone: 203-484-7161
12 Clintonville Road
Fax: 203-484-7118
Gamewell-FCI
Two-zone conventional FACP.
Battery box, required to house two batteries greater than 7
AH, to a maximum of 18 AH.
Dress panel.
Trim ring for semi-flush mounting.
Flex 402 Installation and Maintenance Manual.
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 2 of 2
Flex 402 Two-Zone FACP CS-2402 09/01/06
Specifications
AC power, TB8
Battery (sealed lead-acid only), J8
Initiating device circuits, TB3
Notification appliance circuits, TB2
Form-C relays
Auxiliary outputs
Resettable power, TB1
Cabinet dimensions
120 VAC, 50/60 Hz, 2.3 A.
Wire size: minimum 14 AWG (2.0 mm²)
with 600 V insulation.
Maximum charging circuit: normal flat
charge 27.6 VDC @ 0.8 A.
Maximum battery charger capacity:
18 AH battery. Two 7 AH batteries can
be housed in the FACP cabinet. Larger
batteries require a separate battery
box such as the BB-17F.
Alarm zones 1&2. Power-limited circuitry.
Operation: all zones Style B (Class B).
Normal operating voltage: nominal 22
VDC. Alarm current: 15 mA minimum.
Standby current: 4 mA.
Short circuit current: 40 mA maximum.
Maximum loop resistance: 100 ohms.
End-of-line resistor: 4.7K ohm, 1/2
watt (P/N 71252).
One NAC on Flex 402. Power-limited
circuitry.
Normal operating voltage: nominal 24
VDC.
Maximum signaling current: 2.5 A total
with standard transform.
End-of-line resistor: 4.7K ohm, 1/2
watt (P/N 71252).
Trouble relay TB5 (fail-safe). Alarm
relay TB6.
Contact ratings: 2.0 A @ 30 VAC
(resistive).
Power-limiting circuitry.
Operating voltage: nominal 24 VDC.
Maximum available current: 500 mA,
appropriate for powering four-wire
smoke detectors. Note: Total current
for resettable power and one NAC
must not exceed 3 A for the Flex 402.
Door: 15.342" (38.97 cm) high x 14.677"
(37.28 cm) wide x 0.375" (0.95 cm)
deep. Backbox: 15.0" (38.10 cm) high
x 14.5" (36.83 cm) wide x 3.0" (7.62 cm)
deep.